librenms/librenms

View on GitHub
mibs/ingrasys/IPOMANII-MIB

Summary

Maintainability
Test Coverage
-- Ingrasys iPoManII MIB
-- MIB for Intelligent Power Management 
--
-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) ingrasys(2468)
-- product(1) pduAgent(4) iPoManII(1)
-- ==============================================================================================
---
---     Revision History
---
---     v0.80   20-Apr-2005     Ming Lu/Ingrasys
---                             Created
---
---     v0.81   04-Aug-2007     Ming Lu/Ingrasys
---                             Modify Some error from Web check issue
---                             Add Slave mib data and control
---                             
---     v0.82   04-Oct-2007     Ming Lu/Ingrasys
---                             Modify Some error from Web check issue
---                             
---     v1.00   06-Dec-2007     Ming Lu/Ingrasys
---                             Add Slave trap 26-150
---
---     v1.01   25-Jan-2008     Ming Lu/Ingrasys
---                             Modify Some mib wording error
---                             
---     v1.02   30-Jan-2008     Ming Lu/Ingrasys
---                             Modify Some mib wording error
---                             
---     v1.03   09-Apr-2010     Ming Lu/Ingrasys
---                             Add reset WattItem
---
IPOMANII-MIB DEFINITIONS ::= BEGIN

IMPORTS
  enterprises
    FROM RFC1155-SMI
  OBJECT-TYPE
    FROM RFC-1212
  DisplayString
    FROM RFC1213-MIB
  TRAP-TYPE
    FROM RFC-1215;

ingrasys            OBJECT IDENTIFIER ::= { enterprises 2468 }
product             OBJECT IDENTIFIER ::= { ingrasys 1 }
pduAgent            OBJECT IDENTIFIER ::= { product 4 }
iPoManII              OBJECT IDENTIFIER ::= { pduAgent  2 }
ipmObjects          OBJECT IDENTIFIER ::= { iPoManII 1 }
ipmTraps            OBJECT IDENTIFIER ::= { iPoManII 2 }
                    
ipmIdent            OBJECT IDENTIFIER ::= { ipmObjects 1 }
ipmAgent            OBJECT IDENTIFIER ::= { ipmObjects 2 }
ipmDevice           OBJECT IDENTIFIER ::= { ipmObjects 3 }
ipmSlave            OBJECT IDENTIFIER ::= { ipmObjects 4 }
ipmEnv              OBJECT IDENTIFIER ::= { ipmObjects 5 }

-- ===========================================================================
--
-- ipmIdent
--
--    iPoManII Identification Group
--
-- ===========================================================================
ipmIdentManufacturer OBJECT-TYPE
       SYNTAX DisplayString (SIZE (0..31))
       ACCESS read-write
       STATUS mandatory
       DESCRIPTION
               "The name of manufacturer."
       ::= { ipmIdent 1 }

ipmIdentModel OBJECT-TYPE
      SYNTAX DisplayString (SIZE (0..31))
      ACCESS read-write
      STATUS mandatory
      DESCRIPTION
          "The Model designation of device."
      ::= { ipmIdent 2 }

ipmIdentAgentSoftwareVersion OBJECT-TYPE
       SYNTAX DisplayString (SIZE (0..63))
       ACCESS read-only
       STATUS mandatory
       DESCRIPTION
               "The firmware version of the device."
      ::= { ipmIdent 3 }

ipmIdentName OBJECT-TYPE
      SYNTAX DisplayString (SIZE(0..31))
      ACCESS read-write
      STATUS mandatory
      DESCRIPTION
               "A description of this device."
      ::= { ipmIdent 4 }

ipmAgentConfig    OBJECT IDENTIFIER ::= { ipmAgent 1 }
-- ===========================================================================
--
-- ipmConfig
--
--    iPoManII Configuration Group, configure the secific features of iPoManII
--
-- ===========================================================================
ipmAgentMibVersion OBJECT-TYPE
        SYNTAX INTEGER (1..65500) --
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The Mib Version implemented on this device."
        ::= { ipmAgentConfig 1 }

ipmAgentTime    OBJECT IDENTIFIER ::= { ipmAgent 2 }
-- ===========================================================================
--
-- ipmConfigTime
--
--    Date/Time Configuration Group of the device.
--
-- ===========================================================================
ipmAgentTimeDate OBJECT-TYPE
        SYNTAX DisplayString (SIZE (10..10))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The date in agent, format is (dd/mm/yyyy)"
        ::= { ipmAgentTime 1 }

ipmAgentTimeTime OBJECT-TYPE
        SYNTAX DisplayString (SIZE (8..8))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The time in agent, format is (hh:mm:ss)"
        ::= { ipmAgentTime 2 }

ipmAgentTimerFromNtp OBJECT-TYPE
        SYNTAX  INTEGER {
                enabled(1),
                disabled(2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Enable or disable the agent to synchronize date/time with NTP server."
        ::= { ipmAgentTime 3 }

ipmAgentNtpIpAddress OBJECT-TYPE
       SYNTAX IpAddress
       ACCESS read-write
       STATUS mandatory
       DESCRIPTION
               "The ip address of NTP server."
       ::= { ipmAgentTime 4 }

ipmAgentNtpTimeZone OBJECT-TYPE
        SYNTAX  INTEGER {
                    gMT-1200(1),
                    gMT-1100(2),
                    gMT-1000(3),
                    gMT-0900(4),
                    gMT-0800(5),
                    gMT-0700(6),
                    gMT-0600(7),
                    gMT-0500(8),
                    gMT-0400(9),
                    gMT-0330(10),
                    gMT-0300(11),
                    gMT-0200(12),
                    gMT-0100(13),
                    gMT-0000(14),
                    gMT0100(15),
                    gMT0200(16),
                    gMT0300(17),
                    gMT0330(18),
                    gMT0400(19),
                    gMT0500(20),
                    gMT0530(21),
                    gMT0600(22),
                    gMT0700(23),
                    gMT0800(24),
                    gMT0900(25),
                    gMT1000(26),
                    gMT1100(27),
                    gMT1200(28)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Time Zone to use when synchronize with NTP server."
        ::= { ipmAgentTime 5 }

ipmAgentDayLightSaving OBJECT-TYPE
        SYNTAX  INTEGER {
                enabled(1),
                disabled(2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Enable/disable the Day Light Saving when synchronize with NTP server."
        ::= { ipmAgentTime 6 }

ipmAgentNetwork    OBJECT IDENTIFIER ::= { ipmAgent 3 }
-- ===========================================================================
--
-- ipmConfigNetwork
--
--    Network Configuration Group of the device.
--
-- ===========================================================================

ipmAgentNetworkIp    OBJECT IDENTIFIER ::= { ipmAgentNetwork 1 }
-- ===========================================================================
--
-- ipmAgentNetworkIp
--
--    Ip address Configuration Group of the device.
--
-- ===========================================================================
ipmAgentNetworkIpAdress OBJECT-TYPE
        SYNTAX IpAddress
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The ip address that NMS can identify the managed device."
        ::= { ipmAgentNetworkIp 1}

ipmAgentNetworkIpGateway OBJECT-TYPE
        SYNTAX IpAddress
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The default gateway that allow device managed through routers."
        ::= { ipmAgentNetworkIp 2}

ipmAgentNetworkIpSubnet OBJECT-TYPE
        SYNTAX IpAddress
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Internet address subnet mask"
        ::= { ipmAgentNetworkIp 3}

ipmAgentNetworkDhcpControl OBJECT-TYPE
        SYNTAX  INTEGER {
                enabled(1),
                disabled(2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Enable/disable DHCP protocol"
        ::= { ipmAgentNetwork 2 }

ipmAgentNetworkPingControl OBJECT-TYPE
        SYNTAX  INTEGER {
                enabled(1),
                disabled(2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Enable/disable to response to PING request."
        ::= { ipmAgentNetwork 3 }

ipmAgentNetworkTftpControl OBJECT-TYPE
        SYNTAX  INTEGER {
                enabled(1),
                disabled(2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Enable/disable TFTP protocol"
        ::= { ipmAgentNetwork 4 }

ipmAgentNetworkTelnet    OBJECT IDENTIFIER ::= { ipmAgentNetwork 5 }
-- ===========================================================================
--
-- ipmConfigNetworkTelnet
--
--    Telnet Configuration Group of the device.
--
-- ===========================================================================
ipmAgentTelnetControl OBJECT-TYPE
        SYNTAX  INTEGER {
                enabled(1),
                disabled(2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Enable/disable Telnet protocol."
        ::= { ipmAgentNetworkTelnet 1 }
        
ipmAgentTelnetPort OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The TCP port for telnet"
        ::= { ipmAgentNetworkTelnet 2}

ipmAgentNetworkHttp    OBJECT IDENTIFIER ::= { ipmAgentNetwork 6 }
-- ===========================================================================
--
-- ipmConfigNetworkHttp
--
--    HTTP Configuration Group of the device.
--
-- ===========================================================================
ipmAgentHttpControl OBJECT-TYPE
        SYNTAX  INTEGER {
                enabled(1),
                disabled(2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Enable/disable HTTP protocol."
        ::= { ipmAgentNetworkHttp 1 }
        
ipmAgentHttpPort OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The TCP port for HTTP."
        ::= { ipmAgentNetworkHttp 2}

ipmAgentNetworkSnmp    OBJECT IDENTIFIER ::= { ipmAgentNetwork 7 }
-- ===========================================================================
--
-- ipmAgentNetworkSnmp
--
--    SNMP Configuration Group of the device.
--
-- ===========================================================================
ipmAgentSnmpControl OBJECT-TYPE
        SYNTAX  INTEGER {
                enabled(1),
                disabled(2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Enable/disable SNMP protocol."
        ::= { ipmAgentNetworkSnmp 1 }
        
ipmAgentSnmpPort OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The UDP port for SNMP."
        ::= { ipmAgentNetworkSnmp 2}

ipmAgentLog    OBJECT IDENTIFIER ::= { ipmAgentConfig 4 }
-- ===========================================================================
--
-- ipmConfigLog
--
--    Log Configuration Group of the device.
--
-- ===========================================================================
pduAgentDataLogInterval OBJECT-TYPE
        SYNTAX INTEGER (60..28800) -- in seconds
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The interval of the updation of the data log. The value
                 is in seconds"
        ::= { ipmAgentLog 1 }

ipmAgentControl    OBJECT IDENTIFIER ::= { ipmAgentConfig 5 }
-- ===========================================================================
--
-- ipmAgentAgentControl
--
--    Agent Control Configuration Group of the device.
--
-- ===========================================================================
ipmAgentControlDefault OBJECT-TYPE
        SYNTAX  INTEGER {
                reset(1),
                nothing(2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Reset all parameters of the agent to default value."
        ::= { ipmAgentControl 1}

ipmAgentControlRestart OBJECT-TYPE
        SYNTAX  INTEGER {
                restart(1),
                nothing(2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Restart the agent."
        ::= { ipmAgentControl 2}

ipmAgentTrap    OBJECT IDENTIFIER ::= { ipmAgentConfig 6 }
-- ===========================================================================
--
-- ipmAgentTrap
--
--    Trap Configuration Group of the agent.
--
-- ===========================================================================
ipmAgentTrapRetryCount OBJECT-TYPE
        SYNTAX  INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The count of repeat traps send to NMS before trap
                 acknowledgement received."
        ::= { ipmAgentTrap 1}

ipmAgentTrapRetryTime OBJECT-TYPE
        SYNTAX  INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The time interval in seconds between retry traps sned to NMS."
        ::= { ipmAgentTrap 2}

ipmAgentTrapAckSignature OBJECT-TYPE
        SYNTAX  INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The signature of trap acknowledgement."
        ::= { ipmAgentTrap 3}


-- ===========================================================================
--
-- ipmAgentTrapsReceiversTable
-- 
-- ===========================================================================

ipmAgentTrapsReceiversTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmAgentTrapsReceiversEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of managers to send traps to.  The number of
                 entries is given by the value of agentConfigNumTrapReceivers"
        ::= { ipmAgentConfig 7}

ipmAgentTrapsReceiversEntry OBJECT-TYPE
        SYNTAX IpmAgentTrapsReceiversEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The managers to send traps to."
        INDEX  { trapsIndex }
        ::= { ipmAgentTrapsReceiversTable 1 }

IpmAgentTrapsReceiversEntry ::=
        SEQUENCE {
                trapsIndex              INTEGER,
                trapsReceiverAddr       IpAddress,
                receiverCommunityString DisplayString,
                receiverNmsType         INTEGER,
                receiverSeverityLevel   INTEGER,
                receiverDescription     DisplayString
        }

trapsIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a trap receiver entry."
        ::= { ipmAgentTrapsReceiversEntry 1 }

trapsReceiverAddr OBJECT-TYPE
        SYNTAX IpAddress
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The IP address of the manager to send a trap to."
        ::= { ipmAgentTrapsReceiversEntry 2 }

receiverCommunityString OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..15))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The community name to use in the trap when
                 sent to the manager."
        ::= { ipmAgentTrapsReceiversEntry 3 }

receiverNmsType OBJECT-TYPE
        SYNTAX  INTEGER {
                none(1),
                iPoManII-trap(2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The trap group that NMS desired."
        ::= { ipmAgentTrapsReceiversEntry 4 }

receiverSeverityLevel OBJECT-TYPE
        SYNTAX  INTEGER {
                informational(1),
                warning(2),
                severe(3)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The severity level of traps to be received by this manager."
        ::= { ipmAgentTrapsReceiversEntry 5 }

receiverDescription OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Description of trap receivers"
        ::= { ipmAgentTrapsReceiversEntry 6 }


-- ===========================================================================
--
-- ipmAgentAccessControlTable
-- 
-- ===========================================================================
ipmAgentAccessControlTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmAgentAccessControlEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of managers which can access the device with private
                community string."
        ::= { ipmAgentConfig 8}

ipmAgentAccessControlEntry OBJECT-TYPE
        SYNTAX IpmAgentAccessControlEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The managers."
        INDEX  { accessIndex}
        ::= { ipmAgentAccessControlTable 1 }

IpmAgentAccessControlEntry ::=
        SEQUENCE {
                accessIndex
                        INTEGER,
                accessControlAddr
                        IpAddress,
                accessControlMode
                        INTEGER
        }

accessIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access control entry."
        ::= { ipmAgentAccessControlEntry 1 }

accessControlAddr OBJECT-TYPE
        SYNTAX IpAddress
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The IP address of the manager to access the device."
        ::= { ipmAgentAccessControlEntry 2 }

accessControlMode OBJECT-TYPE
        SYNTAX  INTEGER {
                permitted (1),
                denied (2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Access type, only read/Write access type can change parameter
                 of the device."
        ::= { ipmAgentAccessControlEntry 3 }

ipmDeviceInlet        OBJECT IDENTIFIER ::= { ipmDevice 1 }      
-- ===========================================================================
--
-- ipmDeviceInlet
--
--    Inlet  Group
--
-- ===========================================================================
ipmDeviceInletNumber OBJECT-TYPE
        SYNTAX  INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The inlet number on this device."
        ::= { ipmDeviceInlet 1}

ipmDeviceInletConfigTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmDeviceInletConfigEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of inlet on this device."
        ::= { ipmDeviceInlet 2}

ipmDeviceInletConfigEntry OBJECT-TYPE
        SYNTAX IpmDeviceInletConfigEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The inlet number of device."
        INDEX  { inletConfigIndex}
        ::= { ipmDeviceInletConfigTable 1 }

IpmDeviceInletConfigEntry ::=
        SEQUENCE {
                inletConfigIndex
                        INTEGER,
                inletConfigDesc
                        DisplayString,
                inletConfigVoltageHigh
                        INTEGER,
                inletConfigVoltageHighAction
                        INTEGER,
                inletConfigVoltageLow
                        INTEGER,
                inletConfigVoltageLowAction
                        INTEGER,
                inletConfigCurrentHigh
                        INTEGER,
                inletConfigCurrentHighAction
                        INTEGER,
                inletConfigFrequencyHigh
                        INTEGER,
                inletConfigfrequencyHighAction
                        INTEGER,                
                inletConfigFrequencyLow
                        INTEGER,
                inletConfigfrequencyLowAction
                        INTEGER
        }

inletConfigIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access inlet configuration table."
        ::= { ipmDeviceInletConfigEntry 1 }

inletConfigDesc OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of inlet of device."
        ::= { ipmDeviceInletConfigEntry 2 }

inletConfigVoltageHigh OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Inlet high voltage threshold, in volts."
        ::= { ipmDeviceInletConfigEntry 3 }

inletConfigVoltageHighAction OBJECT-TYPE
        SYNTAX  INTEGER {
                outletsOff (1),
                nothing (2)
                } 
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Reaction of the device when inlet voltage higher than set point."
        ::= { ipmDeviceInletConfigEntry 4 }

inletConfigVoltageLow OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Inlet low voltage threshold, in volts."
        ::= { ipmDeviceInletConfigEntry 5 }

inletConfigVoltageLowAction OBJECT-TYPE
        SYNTAX  INTEGER {
                outletsOff (1),
                nothing (2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Reaction of the device when inlet voltage lower than set point."
        ::= { ipmDeviceInletConfigEntry 6 }
        
inletConfigCurrentHigh OBJECT-TYPE
        SYNTAX INTEGER (1..160) -- 
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Inlet low voltage threshold, in 0.1 amps."
        ::= { ipmDeviceInletConfigEntry 7 }

inletConfigCurrentHighAction OBJECT-TYPE
        SYNTAX  INTEGER {
                outletsOff (1),
                nothing (2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Reaction of the device when inlet current higher than set point."
        ::= { ipmDeviceInletConfigEntry 8 }

inletConfigFrequencyHigh OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Inlet high frequency threshold, in hz."
        ::= { ipmDeviceInletConfigEntry 9 }

inletConfigfrequencyHighAction OBJECT-TYPE
        SYNTAX  INTEGER {
                outletsOff (1),
                nothing (2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Reaction of the device when inlet frequency higher than set point."
        ::= { ipmDeviceInletConfigEntry 10 }

inletConfigFrequencyLow OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Inlet low frequency threshold, in hz."
        ::= { ipmDeviceInletConfigEntry 11 }

inletConfigfrequencyLowAction OBJECT-TYPE
        SYNTAX  INTEGER {
                outletsOff (1),
                nothing (2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Reaction of the device when inlet frequency lower than set point."
        ::= { ipmDeviceInletConfigEntry 12 }

ipmDeviceInletStatusTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmDeviceInletStatusEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of inlet on this device."
        ::= { ipmDeviceInlet 3}

ipmDeviceInletStatusEntry OBJECT-TYPE
        SYNTAX IpmDeviceInletStatusEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The inlet number of device."
        INDEX  { inletStatusIndex}
        ::= { ipmDeviceInletStatusTable 1 }

IpmDeviceInletStatusEntry ::=
        SEQUENCE {
                inletStatusIndex
                        INTEGER,
                inletStatusVoltage
                        INTEGER,
                inletStatusCurrent
                        INTEGER,
                inletStatusFrequency
                        INTEGER,
                inletStatusKwatt
                        INTEGER,
                inletStatusWH
                        INTEGER
        }

inletStatusIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access inlet configuration table."
        ::= { ipmDeviceInletStatusEntry 1 }

inletStatusVoltage OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The Inlet Voltage in 0.1 volts"
        ::= { ipmDeviceInletStatusEntry 2 }
        
inletStatusCurrent OBJECT-TYPE
        SYNTAX INTEGER (0..65500) --
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The Inlet Current in 0.001 Amp."
        ::= { ipmDeviceInletStatusEntry 3 }

inletStatusFrequency OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The Inlet Frequency in 0.1 Hz"
        ::= { ipmDeviceInletStatusEntry 4 }

inletStatusKwatt OBJECT-TYPE
        SYNTAX INTEGER (0..65500) -- 
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The Inlet Kwatt in 0.1 KW/H"
        ::= { ipmDeviceInletStatusEntry 5 }

inletStatusWH OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The Inlet Kwatt in 0.1 W/H"
        ::= { ipmDeviceInletStatusEntry 6 }


inletWattReset OBJECT-TYPE
        SYNTAX INTEGER {
                none(1),
                inlet1(2),
                inlet2(3)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Reset inlet kw."
        ::= { ipmDeviceInlet 4}


ipmDeviceOutlet        OBJECT IDENTIFIER ::= { ipmDevice 2 }      
-- ===========================================================================
--
-- ipmDeviceOutlet
--
--    Inlet  Group
--
-- ===========================================================================
ipmDeviceOutletNumber OBJECT-TYPE
        SYNTAX  INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet number on this device."
        ::= { ipmDeviceOutlet 1}

ipmDeviceOutletConfigTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmDeviceOutletConfigEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of outlet on this device."
        ::= { ipmDeviceOutlet 2}

ipmDeviceOutletConfigEntry OBJECT-TYPE
        SYNTAX IpmDeviceOutletConfigEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The inlet number of device."
        INDEX  { inletConfigIndex}
        ::= { ipmDeviceOutletConfigTable 1 }

IpmDeviceOutletConfigEntry ::=
        SEQUENCE {
                outletConfigIndex
                        INTEGER,
                outletConfigDesc
                        DisplayString,
                outletConfigLocation
                        DisplayString,
                outletConfigOnDelay
                        INTEGER,
                outletConfigOffDelay
                        INTEGER,
                outletConfigCurrentHigh
                        INTEGER,
                outletConfigCurrentHighAction
                        INTEGER
         }

outletConfigIndex OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access inlet configuration table."
        ::= { ipmDeviceOutletConfigEntry 1 }

outletConfigDesc OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of outlet of device."
        ::= { ipmDeviceOutletConfigEntry 2 }

outletConfigLocation OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Location of device connectted to this outlet."
        ::= { ipmDeviceOutletConfigEntry 3 }

outletConfigOnDelay OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmDeviceOutletConfigEntry 4 }

outletConfigOffDelay OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn off tis outlet, in seconds."
        ::= { ipmDeviceOutletConfigEntry 5 }

outletConfigCurrentHigh OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The outlet high current threshold, in amp."
        ::= { ipmDeviceOutletConfigEntry 6 }

outletConfigCurrentHighAction OBJECT-TYPE
        SYNTAX  INTEGER {
                outletOff (1),
                nothing (2)
                } 
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Reaction of the device when outlet current higher than set point."
        ::= { ipmDeviceOutletConfigEntry 7 }

   

ipmDeviceOutletStatusTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmDeviceOutletStatusEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of outlet on this device."
        ::= { ipmDeviceOutlet 3}

ipmDeviceOutletStatusEntry OBJECT-TYPE
        SYNTAX IpmDeviceOutletStatusEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The outlet number of device."
        INDEX  { outletStatusIndex}
        ::= { ipmDeviceOutletStatusTable 1 }

IpmDeviceOutletStatusEntry ::=
        SEQUENCE {
                outletStatusIndex
                        INTEGER,
                outletStatusStatus
                        INTEGER,
                outletStatusCurrent
                        INTEGER,
                outletStatusKwatt
                        INTEGER,
                outletStatusWH
                        INTEGER,
                outletStatusStateTime
                        INTEGER,
                outletStatusTimeToGo
                        INTEGER
        }

outletStatusIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access outlet configuration table."
        ::= { ipmDeviceOutletStatusEntry 1 }

outletStatusStatus OBJECT-TYPE
        SYNTAX  INTEGER {
                unknow (1),
                outletOff (2),
                outletOn (3),
                outletOffToOn (4),
                outletOnToOff (5),
        outletCycling (6)
                }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Outlet state"
        ::= { ipmDeviceOutletStatusEntry 2 }     

outletStatusCurrent OBJECT-TYPE
        SYNTAX INTEGER (0..65500) --
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet Current in 0.001 Amp."
        ::= { ipmDeviceOutletStatusEntry 3 }
        
outletStatusKwatt OBJECT-TYPE
        SYNTAX INTEGER (0..65500) --
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet Kwatt in 0.001 KW/H."
        ::= { ipmDeviceOutletStatusEntry 4 }

outletStatusWH OBJECT-TYPE
        SYNTAX INTEGER (0..65500) --
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet Watt in 0.1 W/H."
        ::= { ipmDeviceOutletStatusEntry 5 }

outletStatusStateTime OBJECT-TYPE
        SYNTAX  INTEGER 
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Time in seconds since the outlet changed to current state."
        ::= { ipmDeviceOutletStatusEntry 6 }     

outletStatusTimeToGo OBJECT-TYPE
        SYNTAX  INTEGER 
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Remain time the outlet state will be changed by agent, in seconds"
        ::= { ipmDeviceOutletStatusEntry 7 }     

ipmDeviceOutletControlTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmDeviceOutletControlEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of outlet on this device."
        ::= { ipmDeviceOutlet 4}

ipmDeviceOutletControlEntry OBJECT-TYPE
        SYNTAX IpmDeviceOutletControlEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The outlet number of device."
        INDEX  { outletControlIndex}
        ::= { ipmDeviceOutletControlTable 1 }

IpmDeviceOutletControlEntry ::=
        SEQUENCE {
                outletControlIndex
                        INTEGER,
                outletControlControl
                        INTEGER
        }

outletControlIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access outlet configuration table."
        ::= { ipmDeviceOutletControlEntry 1 }

outletControlControl OBJECT-TYPE
        SYNTAX INTEGER {
        none(1),
                cancelAction(2),
                onImmediately(3),
                offImmediately(4),
                cycleImmediately(5),
                onByActionTimer(6),
                offByActionTimer(7),
                cycleByActionTimer(8),
                onThenOffByActionTimers(9),
                offThenOnByActionTimers(10)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Set to control the outlet perform action as requested."
        ::= { ipmDeviceOutletControlEntry 2 }

ipmDeviceOutletControlAll OBJECT-TYPE
        SYNTAX INTEGER {
        none(1),
                cancelAction(2),
                onImmediately(3),
                offImmediately(4),
                cycleImmediately(5),
                onByActionTimers(6),
                offByActionTimers(7),
                cycleByActionTimers(8),
                onThenOffByActionTimers(9),
                offThenOnByActionTimers(10)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Set to control all outlets perform action as requested."
        ::= { ipmDeviceOutlet 5}

ipmDeviceOutletWattReset OBJECT-TYPE
        SYNTAX INTEGER {
                none(1),
                outleta(2),
                outletb(3),
                outletc(4),
                outletd(5),
                outlete(6),
                outletf(7),
                
                outletg(8),
                outleth(9),
                outleti(10),
                outletj(11),
                outletk(12),
                outletl(13)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Reset outlet kw."
        ::= { ipmDeviceOutlet 6}


ipmDeviceCcOut        OBJECT IDENTIFIER ::= { ipmDevice 3 }      
-- ===========================================================================
--
-- ipmDeviceCCOut
--
--    Contact Closure Output Group
--
-- ===========================================================================
ipmDeviceCcOutNumber OBJECT-TYPE
        SYNTAX  INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The contact closure output number on this device."
        ::= { ipmDeviceCcOut 1}

ipmDeviceCcOutConfigTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmDeviceCcOutConfigEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of contact closure output on this device."
        ::= { ipmDeviceCcOut 2}

ipmDeviceCcOutConfigEntry OBJECT-TYPE
        SYNTAX IpmDeviceCcOutConfigEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The CC number of device."
        INDEX  { ccOutConfigIndex}
        ::= { ipmDeviceCcOutConfigTable 1 }

IpmDeviceCcOutConfigEntry ::=
        SEQUENCE {
                ccOutConfigIndex
                        INTEGER,
                ccOutConfigDesc
                        DisplayString,
                ccOutConfigEventAction
                        INTEGER,
                ccOutConfigCloseDelay
                        INTEGER,
                ccOutConfigOpenDelay
                        INTEGER
         }

ccOutConfigIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to access contact closure output configuration table."
        ::= { ipmDeviceCcOutConfigEntry 1 }

ccOutConfigDesc OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a contact closure output of device."
        ::= { ipmDeviceCcOutConfigEntry 2 }

ccOutConfigEventAction OBJECT-TYPE
        SYNTAX INTEGER {
        yes (1),
        no (2)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Enable/disble the contact closure output to react to events."
        ::= { ipmDeviceCcOutConfigEntry 3 }

ccOutConfigCloseDelay OBJECT-TYPE
        SYNTAX INTEGER 
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time in seconds when the contact closure output set to close."
        ::= { ipmDeviceCcOutConfigEntry 4 }

ccOutConfigOpenDelay OBJECT-TYPE
        SYNTAX INTEGER 
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time in seconds when the contact closure output set to open."
        ::= { ipmDeviceCcOutConfigEntry 5 }

ipmDeviceCcOutStatusTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmDeviceCcOutStatusEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of contact closure output on this device."
        ::= { ipmDeviceCcOut 3}

ipmDeviceCcOutStatusEntry OBJECT-TYPE
        SYNTAX IpmDeviceCcOutStatusEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The CC number of device."
        INDEX  { ccOutStatusIndex}
        ::= { ipmDeviceCcOutStatusTable 1 }

IpmDeviceCcOutStatusEntry ::=
        SEQUENCE {
                ccOutStatusIndex
                        INTEGER,
                ccOutStatusStatus
                        INTEGER,
                ccOutStatusTimeOnState
                        INTEGER
         }

ccOutStatusIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to access contact closure output configuration table."
        ::= { ipmDeviceCcOutStatusEntry 1 }

ccOutStatusStatus OBJECT-TYPE
        SYNTAX INTEGER {
        closed (1),
        open (2)
    }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "State of a contact closure output of device."
        ::= { ipmDeviceCcOutStatusEntry 2 }

ccOutStatusTimeOnState OBJECT-TYPE
        SYNTAX INTEGER 
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Time in seconds since the contact closure output changed to current state."
        ::= { ipmDeviceCcOutStatusEntry 3 }

ipmDeviceCcOutControlTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmDeviceCcOutControlEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of contact closure output on this device."
        ::= { ipmDeviceCcOut 4}

ipmDeviceCcOutControlEntry OBJECT-TYPE
        SYNTAX IpmDeviceCcOutControlEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The outlet number of device."
        INDEX  { ccOutControlIndex}
        ::= { ipmDeviceCcOutControlTable 1 }

IpmDeviceCcOutControlEntry ::=
        SEQUENCE {
                ccOutControlIndex
                        INTEGER,
        ccOutControlControl
            INTEGER
        }

ccOutControlIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access contact closure output configuration table."
        ::= { ipmDeviceCcOutControlEntry 1 }

ccOutControlControl OBJECT-TYPE
        SYNTAX INTEGER {
        none(1),
                cancelAction(2),
                closeImmediately(3),
                openImmediately(4),
                cycleImmediately(5),
                closeByCloseTimer(6),
                openByOpenTimer(7),
                cycleByActionTimer(8),
                closeThenOpenByActionTimers(9),
                openThenCloseByActionTimers(10)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Set to control the contact closure output perform action as requested."
        ::= { ipmDeviceCcOutControlEntry 2 }

ipmSlaveState        OBJECT IDENTIFIER ::= { ipmSlave 1 }      
-- ===========================================================================
-- 
-- ipmSlaveState
-- 
--     Daisy Chain Device Group
-- 
-- ===========================================================================
--

ipmSlaveStateTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmSlaveStateEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of outlet on this device."
        ::= { ipmSlaveState 1}

ipmSlaveStateEntry OBJECT-TYPE
        SYNTAX IpmSlaveStateEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The outlet number of device."
        INDEX  { slaveStateIndex}
        ::= { ipmSlaveStateTable 1 }

IpmSlaveStateEntry ::=
        SEQUENCE {
                slaveStateIndex
                        INTEGER,
                slaveStateControl01
                        INTEGER
        }

slaveStateIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access outlet configuration table."
        ::= { ipmSlaveStateEntry 1 }

slaveStateControl01 OBJECT-TYPE
        SYNTAX INTEGER {
                disconnected(1),
                connected(2)
    }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Set to control the outlet perform action as requested to slave outlet A"
        ::= { ipmSlaveStateEntry 2 }

ipmSlaveInlet        OBJECT IDENTIFIER ::= { ipmSlave 2 }      
-- ===========================================================================
-- 
-- ipmSlaveAllDevice
-- 
--     Daisy Chain Device Group
-- 
-- ===========================================================================

ipmSlaveInletStatus        OBJECT IDENTIFIER ::= { ipmSlaveInlet 1 }      
-- ===========================================================================
-- 
-- ipmSlaveAllDevice
-- 
--     Daisy Chain Device Group
-- 
-- ===========================================================================


ipmDeviceSlaveInletStatusTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmDeviceSlaveInletStatusEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of inlet on this device."
        ::= { ipmSlaveInletStatus 1}

ipmDeviceSlaveInletStatusEntry OBJECT-TYPE
        SYNTAX IpmDeviceSlaveInletStatusEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The inlet number of device."
        INDEX  { inletStatusIndex}
        ::= { ipmDeviceSlaveInletStatusTable 1 }

IpmDeviceSlaveInletStatusEntry ::=
        SEQUENCE {
                inletSlaveStatusIndex
                        INTEGER,
                inletSlaveStatusVoltage
                        INTEGER,
                inletSlaveStatusCurrent
                        INTEGER,
                inletSlaveStatusFrequency
                        INTEGER,
                inletSlaveStatusKwatt
                        INTEGER,
                inletSlaveStatusWH
                        INTEGER,
                inletSlaveStatusVoltage2
                        INTEGER,
                inletSlaveStatusCurrent2
                        INTEGER,
                inletSlaveStatusFrequency2
                        INTEGER,
                inletSlaveStatusKwatt2
                        INTEGER,
                inletSlaveStatusWH2
                        INTEGER
        }

inletSlaveStatusIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access inlet configuration table."
        ::= { ipmDeviceSlaveInletStatusEntry 1 }

inletSlaveStatusVoltage OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The Inlet Voltage in 0.1 volts"
        ::= { ipmDeviceSlaveInletStatusEntry 2 }
        
inletSlaveStatusCurrent OBJECT-TYPE
        SYNTAX INTEGER (0..65500) --
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The Inlet Current in 0.001 Amp."
        ::= { ipmDeviceSlaveInletStatusEntry 3 }

inletSlaveStatusFrequency OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The Inlet Frequency in 0.1 Hz"
        ::= { ipmDeviceSlaveInletStatusEntry 4 }

inletSlaveStatusKwatt OBJECT-TYPE
        SYNTAX INTEGER (0..65500) -- 
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The Inlet Kwatt in 0.001 KW/H"
        ::= { ipmDeviceSlaveInletStatusEntry 5 }

inletSlaveStatusWH OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The Inlet Kwatt in 0.001 KW/H"
        ::= { ipmDeviceSlaveInletStatusEntry 6 }

inletSlaveStatusVoltage2 OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The Inlet Voltage in 0.1 volts"
        ::= { ipmDeviceSlaveInletStatusEntry 7 }
        
inletSlaveStatusCurrent2 OBJECT-TYPE
        SYNTAX INTEGER (0..65500) --
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The Inlet Current in 0.001 Amp."
        ::= { ipmDeviceSlaveInletStatusEntry 8 }

inletSlaveStatusFrequency2 OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The Inlet Frequency in 0.1 Hz"
        ::= { ipmDeviceSlaveInletStatusEntry 9 }

inletSlaveStatusKwatt2 OBJECT-TYPE
        SYNTAX INTEGER (0..65500) -- 
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The Inlet Kwatt in 0.001 KW/H"
        ::= { ipmDeviceSlaveInletStatusEntry 10 }

inletSlaveStatusWH2 OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The Inlet Kwatt in 0.001 KW/H"
        ::= { ipmDeviceSlaveInletStatusEntry 11 }

ipmSlaveInletConfig        OBJECT IDENTIFIER ::= { ipmSlaveInlet 2 }      
-- ===========================================================================
-- 
-- ipmSlaveAllDevice
-- 
--     Daisy Chain Device Group
-- 
-- ===========================================================================


ipmDeviceslaveInletConfigTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmDeviceslaveInletConfigEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of inlet on this device."
        ::= { ipmSlaveInletConfig 1}

ipmDeviceslaveInletConfigEntry OBJECT-TYPE
        SYNTAX IpmDeviceslaveInletConfigEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The inlet number of device."
        INDEX  { slaveInletConfigIndex}
        ::= { ipmDeviceslaveInletConfigTable 1 }

IpmDeviceslaveInletConfigEntry ::=
        SEQUENCE {
                slaveInletConfigIndex
                        INTEGER,
                slaveInletConfigVoltageHigh
                        INTEGER,
                slaveInletConfigVoltageLow
                        INTEGER,
                slaveInlet2ConfigVoltageHigh
                        INTEGER,
                slaveInlet2ConfigVoltageLow
                        INTEGER
        }

slaveInletConfigIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access inlet configuration table."
        ::= { ipmDeviceslaveInletConfigEntry 1 }


slaveInletConfigVoltageHigh OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Inlet high voltage threshold, in volts."
        ::= { ipmDeviceslaveInletConfigEntry 2 }


slaveInletConfigVoltageLow OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Inlet low voltage threshold, in volts."
        ::= { ipmDeviceslaveInletConfigEntry 3 }

        
slaveInlet2ConfigVoltageHigh OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Inlet 2 high voltage threshold, in volts."
        ::= { ipmDeviceslaveInletConfigEntry 4 }

slaveInlet2ConfigVoltageLow OBJECT-TYPE
        SYNTAX INTEGER (1..65500) -- 
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Inlet low voltage threshold, in volts."
        ::= { ipmDeviceslaveInletConfigEntry 5 }


ipmSlaveOutlet        OBJECT IDENTIFIER ::= { ipmSlave 3 }      
-- ===========================================================================
-- 
-- ipmSlaveAllDevice
-- 
--     Daisy Chain Device Group
-- 
-- ===========================================================================

ipmSlaveOutletConfig        OBJECT IDENTIFIER ::= { ipmSlaveOutlet 1 }      
-- ===========================================================================
-- 
-- ipmOutletConfig
-- 
--     Outlet Config Group
-- 
-- ===========================================================================

--
-- Outlet Name Description
--

ipmSlaveDeviceOutletNameTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmSlaveDeviceOutletNameEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of outlet on this device."
        ::= { ipmSlaveOutletConfig 1}

ipmSlaveDeviceOutletNameEntry OBJECT-TYPE
        SYNTAX IpmSlaveDeviceOutletNameEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The outlet number of device."
        INDEX  { slaveOutletNameIndex}
        ::= { ipmSlaveDeviceOutletNameTable 1 }

IpmSlaveDeviceOutletNameEntry ::=
        SEQUENCE {
                slaveOutletNameIndex
                        INTEGER,
                slaveOutletName01
                        DisplayString,
                slaveOutletName02
                        DisplayString,
                slaveOutletName03
                        DisplayString,
                slaveOutletName04
                        DisplayString,
                slaveOutletName05
                        DisplayString,
                slaveOutletName06
                        DisplayString,
                slaveOutletName07
                        DisplayString,
                slaveOutletName08
                        DisplayString,
                slaveOutletName09
                        DisplayString,
                slaveOutletName10
                        DisplayString,
                slaveOutletName11
                        DisplayString,
                slaveOutletName12
                        DisplayString
        }

slaveOutletNameIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access outlet configuration table."
        ::= { ipmSlaveDeviceOutletNameEntry 1 }

slaveOutletName01 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletNameEntry 2 }

slaveOutletName02 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletNameEntry 3 }

slaveOutletName03 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletNameEntry 4 }

slaveOutletName04 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletNameEntry 5 }

slaveOutletName05 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletNameEntry 6 }

slaveOutletName06 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletNameEntry 7 }

slaveOutletName07 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletNameEntry 8 }

slaveOutletName08 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletNameEntry 9 }

slaveOutletName09 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletNameEntry 10 }

slaveOutletName10 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletNameEntry 11 }

slaveOutletName11 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletNameEntry 12 }

slaveOutletName12 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletNameEntry 13 }

-- ===============================
-- Outlet Location Description
-- ===============================


ipmSlaveDeviceOutletLocationTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmSlaveDeviceOutletLocationEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of outlet on this device."
        ::= { ipmSlaveOutletConfig 2}

ipmSlaveDeviceOutletLocationEntry OBJECT-TYPE
        SYNTAX IpmSlaveDeviceOutletLocationEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The outlet number of device."
        INDEX  { slaveOutletLocationIndex}
        ::= { ipmSlaveDeviceOutletLocationTable 1 }

IpmSlaveDeviceOutletLocationEntry ::=
        SEQUENCE {
                slaveOutletLocationIndex
                        INTEGER,
                slaveOutletLocation01
                        DisplayString,
                slaveOutletLocation02
                        DisplayString,
                slaveOutletLocation03
                        DisplayString,
                slaveOutletLocation04
                        DisplayString,
                slaveOutletLocation05
                        DisplayString,
                slaveOutletLocation06
                        DisplayString,
                slaveOutletLocation07
                        DisplayString,
                slaveOutletLocation08
                        DisplayString,
                slaveOutletLocation09
                        DisplayString,
                slaveOutletLocation10
                        DisplayString,
                slaveOutletLocation11
                        DisplayString,
                slaveOutletLocation12
                        DisplayString
        }

slaveOutletLocationIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access outlet configuration table."
        ::= { ipmSlaveDeviceOutletLocationEntry 1 }

slaveOutletLocation01 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletLocationEntry 2 }

slaveOutletLocation02 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletLocationEntry 3 }

slaveOutletLocation03 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletLocationEntry 4 }

slaveOutletLocation04 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletLocationEntry 5 }

slaveOutletLocation05 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletLocationEntry 6 }

slaveOutletLocation06 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletLocationEntry 7 }

slaveOutletLocation07 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletLocationEntry 8 }

slaveOutletLocation08 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletLocationEntry 9 }

slaveOutletLocation09 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletLocationEntry 10 }

slaveOutletLocation10 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletLocationEntry 11 }

slaveOutletLocation11 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletLocationEntry 12 }

slaveOutletLocation12 OBJECT-TYPE
        SYNTAX DisplayString (SIZE(0..31))
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A Description of a outlet name of device."
        ::= { ipmSlaveDeviceOutletLocationEntry 13 }

-- ==========================================
-- Outlet On Delay Time
-- ==========================================

ipmSlaveDeviceOutletOnTimeTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmSlaveDeviceOutletOnTimeEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of outlet on this device."
        ::= { ipmSlaveOutletConfig 3}

ipmSlaveDeviceOutletOnTimeEntry OBJECT-TYPE
        SYNTAX IpmSlaveDeviceOutletOnTimeEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The outlet number of device."
        INDEX  { slaveOutletOnTimeIndex}
        ::= { ipmSlaveDeviceOutletOnTimeTable 1 }

IpmSlaveDeviceOutletOnTimeEntry ::=
        SEQUENCE {
                slaveOutletOnTimeIndex
                        INTEGER,
                slaveOutletOnTime01
                        INTEGER,
                slaveOutletOnTime02
                        INTEGER,
                slaveOutletOnTime03
                        INTEGER,
                slaveOutletOnTime04
                        INTEGER,
                slaveOutletOnTime05
                        INTEGER,
                slaveOutletOnTime06
                        INTEGER,
                slaveOutletOnTime07
                        INTEGER,
                slaveOutletOnTime08
                        INTEGER,
                slaveOutletOnTime09
                        INTEGER,
                slaveOutletOnTime10
                        INTEGER,
                slaveOutletOnTime11
                        INTEGER,
                slaveOutletOnTime12
                        INTEGER
        }

slaveOutletOnTimeIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access outlet configuration table."
        ::= { ipmSlaveDeviceOutletOnTimeEntry 1 }

slaveOutletOnTime01 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOnTimeEntry 2 }

slaveOutletOnTime02 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOnTimeEntry 3 }

slaveOutletOnTime03 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOnTimeEntry 4 }

slaveOutletOnTime04 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOnTimeEntry 5 }

slaveOutletOnTime05 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOnTimeEntry 6 }

slaveOutletOnTime06 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOnTimeEntry 7 }

slaveOutletOnTime07 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOnTimeEntry 8 }

slaveOutletOnTime08 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOnTimeEntry 9 }

slaveOutletOnTime09 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOnTimeEntry 10 }

slaveOutletOnTime10 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOnTimeEntry 11 }


slaveOutletOnTime11 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOnTimeEntry 12 }

slaveOutletOnTime12 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOnTimeEntry 13 }

-- ==========================================
-- Outlet Off Delay Time
-- ==========================================

ipmSlaveDeviceOutletOffTimeTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmSlaveDeviceOutletOffTimeEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of outlet on this device."
        ::= { ipmSlaveOutletConfig 4}

ipmSlaveDeviceOutletOffTimeEntry OBJECT-TYPE
        SYNTAX IpmSlaveDeviceOutletOffTimeEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The outlet number of device."
        INDEX  { slaveOutletOffTimeIndex}
        ::= { ipmSlaveDeviceOutletOffTimeTable 1 }

IpmSlaveDeviceOutletOffTimeEntry ::=
        SEQUENCE {
                slaveOutletOffTimeIndex
                        INTEGER,
                slaveOutletOffTime01
                        INTEGER,
                slaveOutletOffTime02
                        INTEGER,
                slaveOutletOffTime03
                        INTEGER,
                slaveOutletOffTime04
                        INTEGER,
                slaveOutletOffTime05
                        INTEGER,
                slaveOutletOffTime06
                        INTEGER,
                slaveOutletOffTime07
                        INTEGER,
                slaveOutletOffTime08
                        INTEGER,
                slaveOutletOffTime09
                        INTEGER,
                slaveOutletOffTime10
                        INTEGER,
                slaveOutletOffTime11
                        INTEGER,
                slaveOutletOffTime12
                        INTEGER
        }

slaveOutletOffTimeIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access outlet configuration table."
        ::= { ipmSlaveDeviceOutletOffTimeEntry 1 }

slaveOutletOffTime01 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOffTimeEntry 2 }

slaveOutletOffTime02 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOffTimeEntry 3 }

slaveOutletOffTime03 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOffTimeEntry 4 }

slaveOutletOffTime04 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOffTimeEntry 5 }

slaveOutletOffTime05 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOffTimeEntry 6 }

slaveOutletOffTime06 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOffTimeEntry 7 }

slaveOutletOffTime07 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOffTimeEntry 8 }

slaveOutletOffTime08 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOffTimeEntry 9 }

slaveOutletOffTime09 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOffTimeEntry 10 }

slaveOutletOffTime10 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOffTimeEntry 11 }


slaveOutletOffTime11 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOffTimeEntry 12 }

slaveOutletOffTime12 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay time before turn on tis outlet, in seconds."
        ::= { ipmSlaveDeviceOutletOffTimeEntry 13 }


-- ==========================================
-- Outlet Current TH
-- ==========================================

ipmSlaveDeviceOutletCurrThTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmSlaveDeviceOutletCurrThEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of outlet on this device."
        ::= { ipmSlaveOutletConfig 5}

ipmSlaveDeviceOutletCurrThEntry OBJECT-TYPE
        SYNTAX IpmSlaveDeviceOutletCurrThEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The outlet number of device."
        INDEX  { slaveOutletCurrThIndex}
        ::= { ipmSlaveDeviceOutletCurrThTable 1 }

IpmSlaveDeviceOutletCurrThEntry ::=
        SEQUENCE {
                slaveOutletCurrThIndex
                        INTEGER,
                slaveOutletCurrTh01
                        INTEGER,
                slaveOutletCurrTh02
                        INTEGER,
                slaveOutletCurrTh03
                        INTEGER,
                slaveOutletCurrTh04
                        INTEGER,
                slaveOutletCurrTh05
                        INTEGER,
                slaveOutletCurrTh06
                        INTEGER,
                slaveOutletCurrTh07
                        INTEGER,
                slaveOutletCurrTh08
                        INTEGER,
                slaveOutletCurrTh09
                        INTEGER,
                slaveOutletCurrTh10
                        INTEGER,
                slaveOutletCurrTh11
                        INTEGER,
                slaveOutletCurrTh12
                        INTEGER
        }

slaveOutletCurrThIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access outlet configuration table."
        ::= { ipmSlaveDeviceOutletCurrThEntry 1 }

slaveOutletCurrTh01 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Outlet Current Threshold ,in 0.1 Amp."
        ::= { ipmSlaveDeviceOutletCurrThEntry 2 }

slaveOutletCurrTh02 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Outlet Current Threshold ,in 0.1 Amp."
        ::= { ipmSlaveDeviceOutletCurrThEntry 3 }

slaveOutletCurrTh03 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Outlet Current Threshold ,in 0.1 Amp."
        ::= { ipmSlaveDeviceOutletCurrThEntry 4 }

slaveOutletCurrTh04 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Outlet Current Threshold ,in 0.1 Amp."
        ::= { ipmSlaveDeviceOutletCurrThEntry 5 }

slaveOutletCurrTh05 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Outlet Current Threshold ,in 0.1 Amp."
        ::= { ipmSlaveDeviceOutletCurrThEntry 6 }

slaveOutletCurrTh06 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Outlet Current Threshold ,in 0.1 Amp."
        ::= { ipmSlaveDeviceOutletCurrThEntry 7 }

slaveOutletCurrTh07 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Outlet Current Threshold ,in 0.1 Amp."
        ::= { ipmSlaveDeviceOutletCurrThEntry 8 }

slaveOutletCurrTh08 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Outlet Current Threshold ,in 0.1 Amp."
        ::= { ipmSlaveDeviceOutletCurrThEntry 9 }

slaveOutletCurrTh09 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Outlet Current Threshold ,in 0.1 Amp."
        ::= { ipmSlaveDeviceOutletCurrThEntry 10 }

slaveOutletCurrTh10 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Outlet Current Threshold ,in 0.1 Amp."
        ::= { ipmSlaveDeviceOutletCurrThEntry 11 }


slaveOutletCurrTh11 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Outlet Current Threshold ,in 0.1 Amp."
        ::= { ipmSlaveDeviceOutletCurrThEntry 12 }

slaveOutletCurrTh12 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The Outlet Current Threshold ,in 0.1 Amp."
        ::= { ipmSlaveDeviceOutletCurrThEntry 13 }

ipmSlaveOutletStatus        OBJECT IDENTIFIER ::= { ipmSlaveOutlet 2 }      
-- ===========================================================================
-- 
-- ipmOutletStatus
-- 
--     Outlet Status Group
-- 
-- ===========================================================================
-- ==========================================
-- Outlet Current
-- ==========================================

ipmSlaveDeviceOutletCurrentTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmSlaveDeviceOutletCurrentEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of outlet on this device."
        ::= { ipmSlaveOutletStatus 1}

ipmSlaveDeviceOutletCurrentEntry OBJECT-TYPE
        SYNTAX IpmSlaveDeviceOutletCurrentEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The outlet number of device."
        INDEX  { slaveOutletCurrentIndex}
        ::= { ipmSlaveDeviceOutletCurrentTable 1 }

IpmSlaveDeviceOutletCurrentEntry ::=
        SEQUENCE {
                slaveOutletCurrentIndex
                        INTEGER,
                slaveOutletCurrent01
                        INTEGER,
                slaveOutletCurrent02
                        INTEGER,
                slaveOutletCurrent03
                        INTEGER,
                slaveOutletCurrent04
                        INTEGER,
                slaveOutletCurrent05
                        INTEGER,
                slaveOutletCurrent06
                        INTEGER,
                slaveOutletCurrent07
                        INTEGER,
                slaveOutletCurrent08
                        INTEGER,
                slaveOutletCurrent09
                        INTEGER,
                slaveOutletCurrent10
                        INTEGER,
                slaveOutletCurrent11
                        INTEGER,
                slaveOutletCurrent12
                        INTEGER
        }

slaveOutletCurrentIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access outlet configuration table."
        ::= { ipmSlaveDeviceOutletCurrentEntry 1 }

slaveOutletCurrent01 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet A Current in 0.001 Amp."
        ::= { ipmSlaveDeviceOutletCurrentEntry 2 }

slaveOutletCurrent02 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet B Current in 0.001 Amp."
        ::= { ipmSlaveDeviceOutletCurrentEntry 3 }

slaveOutletCurrent03 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet C Current in 0.001 Amp."
        ::= { ipmSlaveDeviceOutletCurrentEntry 4 }

slaveOutletCurrent04 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet D Current in 0.001 Amp."
        ::= { ipmSlaveDeviceOutletCurrentEntry 5 }

slaveOutletCurrent05 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet E Current in 0.001 Amp."
        ::= { ipmSlaveDeviceOutletCurrentEntry 6 }

slaveOutletCurrent06 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet F Current in 0.001 Amp."
        ::= { ipmSlaveDeviceOutletCurrentEntry 7 }

slaveOutletCurrent07 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet G Current in 0.001 Amp."
        ::= { ipmSlaveDeviceOutletCurrentEntry 8 }

slaveOutletCurrent08 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet H Current in 0.001 Amp."
        ::= { ipmSlaveDeviceOutletCurrentEntry 9 }

slaveOutletCurrent09 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet I Current in 0.001 Amp."
        ::= { ipmSlaveDeviceOutletCurrentEntry 10 }

slaveOutletCurrent10 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet J Current in 0.001 Amp."
        ::= { ipmSlaveDeviceOutletCurrentEntry 11 }


slaveOutletCurrent11 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet K Current in 0.001 Amp."
        ::= { ipmSlaveDeviceOutletCurrentEntry 12 }

slaveOutletCurrent12 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet L Current in 0.001 Amp."
        ::= { ipmSlaveDeviceOutletCurrentEntry 13 }

-- ==========================================
-- Outlet W/H
-- ==========================================

ipmSlaveDeviceOutletWattTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmSlaveDeviceOutletWattEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of outlet on this device."
        ::= { ipmSlaveOutletStatus 2}

ipmSlaveDeviceOutletWattEntry OBJECT-TYPE
        SYNTAX IpmSlaveDeviceOutletWattEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The outlet number of device."
        INDEX  { slaveOutletWattIndex}
        ::= { ipmSlaveDeviceOutletWattTable 1 }

IpmSlaveDeviceOutletWattEntry ::=
        SEQUENCE {
                slaveOutletWattIndex
                        INTEGER,
                slaveOutletWatt01
                        INTEGER,
                slaveOutletWatt02
                        INTEGER,
                slaveOutletWatt03
                        INTEGER,
                slaveOutletWatt04
                        INTEGER,
                slaveOutletWatt05
                        INTEGER,
                slaveOutletWatt06
                        INTEGER,
                slaveOutletWatt07
                        INTEGER,
                slaveOutletWatt08
                        INTEGER,
                slaveOutletWatt09
                        INTEGER,
                slaveOutletWatt10
                        INTEGER,
                slaveOutletWatt11
                        INTEGER,
                slaveOutletWatt12
                        INTEGER
        }

slaveOutletWattIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access outlet configuration table."
        ::= { ipmSlaveDeviceOutletWattEntry 1 }

slaveOutletWatt01 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet A Watt in 0.1 W/H."
        ::= { ipmSlaveDeviceOutletWattEntry 2 }

slaveOutletWatt02 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet B Watt in 0.1 W/H."
        ::= { ipmSlaveDeviceOutletWattEntry 3 }

slaveOutletWatt03 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet C Watt in 0.1 W/H."
        ::= { ipmSlaveDeviceOutletWattEntry 4 }

slaveOutletWatt04 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet D Watt in 0.1 W/H."
        ::= { ipmSlaveDeviceOutletWattEntry 5 }

slaveOutletWatt05 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet E Watt in 0.1 W/H."
        ::= { ipmSlaveDeviceOutletWattEntry 6 }

slaveOutletWatt06 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet F Watt in 0.1 W/H."
        ::= { ipmSlaveDeviceOutletWattEntry 7 }

slaveOutletWatt07 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet G Watt in 0.1 W/H."
        ::= { ipmSlaveDeviceOutletWattEntry 8 }

slaveOutletWatt08 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet H Watt in 0.1 W/H."
        ::= { ipmSlaveDeviceOutletWattEntry 9 }

slaveOutletWatt09 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet I Watt in 0.1 W/H."
        ::= { ipmSlaveDeviceOutletWattEntry 10 }

slaveOutletWatt10 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet J Watt in 0.1 W/H."
        ::= { ipmSlaveDeviceOutletWattEntry 11 }


slaveOutletWatt11 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet K Watt in 0.1 W/H."
        ::= { ipmSlaveDeviceOutletWattEntry 12 }

slaveOutletWatt12 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet L Watt in 0.1 W/H."
        ::= { ipmSlaveDeviceOutletWattEntry 13 }

-- ==========================================
-- Outlet W/H
-- ==========================================

ipmSlaveDeviceOutletKwattTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmSlaveDeviceOutletKwattEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of outlet on this device."
        ::= { ipmSlaveOutletStatus 3}

ipmSlaveDeviceOutletKwattEntry OBJECT-TYPE
        SYNTAX IpmSlaveDeviceOutletKwattEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The outlet number of device."
        INDEX  { slaveOutletKwattIndex}
        ::= { ipmSlaveDeviceOutletKwattTable 1 }

IpmSlaveDeviceOutletKwattEntry ::=
        SEQUENCE {
                slaveOutletKwattIndex
                        INTEGER,
                slaveOutletKwatt01
                        INTEGER,
                slaveOutletKwatt02
                        INTEGER,
                slaveOutletKwatt03
                        INTEGER,
                slaveOutletKwatt04
                        INTEGER,
                slaveOutletKwatt05
                        INTEGER,
                slaveOutletKwatt06
                        INTEGER,
                slaveOutletKwatt07
                        INTEGER,
                slaveOutletKwatt08
                        INTEGER,
                slaveOutletKwatt09
                        INTEGER,
                slaveOutletKwatt10
                        INTEGER,
                slaveOutletKwatt11
                        INTEGER,
                slaveOutletKwatt12
                        INTEGER
        }

slaveOutletKwattIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access outlet configuration table."
        ::= { ipmSlaveDeviceOutletKwattEntry 1 }

slaveOutletKwatt01 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet A Kwatt in 0.001 KW/H."
        ::= { ipmSlaveDeviceOutletKwattEntry 2 }

slaveOutletKwatt02 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet B Kwatt in 0.001 KW/H."
        ::= { ipmSlaveDeviceOutletKwattEntry 3 }

slaveOutletKwatt03 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet C Kwatt in 0.001 KW/H."
        ::= { ipmSlaveDeviceOutletKwattEntry 4 }

slaveOutletKwatt04 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet D Kwatt in 0.001 KW/H."
        ::= { ipmSlaveDeviceOutletKwattEntry 5 }

slaveOutletKwatt05 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet E Kwatt in 0.001 KW/H."
        ::= { ipmSlaveDeviceOutletKwattEntry 6 }

slaveOutletKwatt06 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet F Kwatt in 0.001 KW/H."
        ::= { ipmSlaveDeviceOutletKwattEntry 7 }

slaveOutletKwatt07 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet G Kwatt in 0.001 KW/H."
        ::= { ipmSlaveDeviceOutletKwattEntry 8 }

slaveOutletKwatt08 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet H Kwatt in 0.001 KW/H."
        ::= { ipmSlaveDeviceOutletKwattEntry 9 }

slaveOutletKwatt09 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet I Kwatt in 0.001 KW/H."
        ::= { ipmSlaveDeviceOutletKwattEntry 10 }

slaveOutletKwatt10 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet J Kwatt in 0.001 KW/H."
        ::= { ipmSlaveDeviceOutletKwattEntry 11 }


slaveOutletKwatt11 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet K Kwatt in 0.001 KW/H."
        ::= { ipmSlaveDeviceOutletKwattEntry 12 }

slaveOutletKwatt12 OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The outlet L Kwatt in 0.001 KW/H."
        ::= { ipmSlaveDeviceOutletKwattEntry 13 }


ipmSlaveOutletAction        OBJECT IDENTIFIER ::= { ipmSlaveOutlet 3 }      
-- ===========================================================================
-- 
-- ipmOutletStatus
-- 
--     Outlet Action Group
-- 
-- ===========================================================================

ipmSlaveDeviceOutletActionTable OBJECT-TYPE
        SYNTAX SEQUENCE OF IpmSlaveDeviceOutletActionEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of outlet on this device."
        ::= { ipmSlaveOutletAction 1}

ipmSlaveDeviceOutletActionEntry OBJECT-TYPE
        SYNTAX IpmSlaveDeviceOutletActionEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The outlet number of device."
        INDEX  { slaveOutletActionIndex}
        ::= { ipmSlaveDeviceOutletActionTable 1 }

IpmSlaveDeviceOutletActionEntry ::=
        SEQUENCE {
                slaveOutletActionIndex
                        INTEGER,
                slaveOutletAction01
                        INTEGER,
                slaveOutletAction02
                        INTEGER,
                slaveOutletAction03
                        INTEGER,
                slaveOutletAction04
                        INTEGER,
                slaveOutletAction05
                        INTEGER,
                slaveOutletAction06
                        INTEGER,
                slaveOutletAction07
                        INTEGER,
                slaveOutletAction08
                        INTEGER,
                slaveOutletAction09
                        INTEGER,
                slaveOutletAction10
                        INTEGER,
                slaveOutletAction11
                        INTEGER,
                slaveOutletAction12
                        INTEGER
        }

slaveOutletActionIndex OBJECT-TYPE
        SYNTAX INTEGER (0..65535)
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a access outlet configuration table."
        ::= { ipmSlaveDeviceOutletActionEntry 1 }

slaveOutletAction01 OBJECT-TYPE
        SYNTAX INTEGER {
        none(1),
        cancelAction(2),
        onImmediately(3),
        offImmediately(4),
        cycleImmediately(5),
        onByActionTimer(6),
        offByActionTimer(7),
        cycleByActionTimer(8),
        onThenOffByActionTimers(9),
        offThenOnByActionTimers(10)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Set to control the outlet perform action as requested."
        ::= { ipmSlaveDeviceOutletActionEntry 2 }

slaveOutletAction02 OBJECT-TYPE
        SYNTAX INTEGER {
        none(1),
        cancelAction(2),
        onImmediately(3),
        offImmediately(4),
        cycleImmediately(5),
        onByActionTimer(6),
        offByActionTimer(7),
        cycleByActionTimer(8),
        onThenOffByActionTimers(9),
        offThenOnByActionTimers(10)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Set to control the outlet perform action as requested."
        ::= { ipmSlaveDeviceOutletActionEntry 3 }

slaveOutletAction03 OBJECT-TYPE
        SYNTAX INTEGER {
        none(1),
        cancelAction(2),
        onImmediately(3),
        offImmediately(4),
        cycleImmediately(5),
        onByActionTimer(6),
        offByActionTimer(7),
        cycleByActionTimer(8),
        onThenOffByActionTimers(9),
        offThenOnByActionTimers(10)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Set to control the outlet perform action as requested."
        ::= { ipmSlaveDeviceOutletActionEntry 4 }

slaveOutletAction04 OBJECT-TYPE
        SYNTAX INTEGER {
        none(1),
        cancelAction(2),
        onImmediately(3),
        offImmediately(4),
        cycleImmediately(5),
        onByActionTimer(6),
        offByActionTimer(7),
        cycleByActionTimer(8),
        onThenOffByActionTimers(9),
        offThenOnByActionTimers(10)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Set to control the outlet perform action as requested."
        ::= { ipmSlaveDeviceOutletActionEntry 5 }

slaveOutletAction05 OBJECT-TYPE
        SYNTAX INTEGER {
        none(1),
        cancelAction(2),
        onImmediately(3),
        offImmediately(4),
        cycleImmediately(5),
        onByActionTimer(6),
        offByActionTimer(7),
        cycleByActionTimer(8),
        onThenOffByActionTimers(9),
        offThenOnByActionTimers(10)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Set to control the outlet perform action as requested."
        ::= { ipmSlaveDeviceOutletActionEntry 6 }

slaveOutletAction06 OBJECT-TYPE
        SYNTAX INTEGER {
        none(1),
        cancelAction(2),
        onImmediately(3),
        offImmediately(4),
        cycleImmediately(5),
        onByActionTimer(6),
        offByActionTimer(7),
        cycleByActionTimer(8),
        onThenOffByActionTimers(9),
        offThenOnByActionTimers(10)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Set to control the outlet perform action as requested."
        ::= { ipmSlaveDeviceOutletActionEntry 7 }

slaveOutletAction07 OBJECT-TYPE
        SYNTAX INTEGER {
        none(1),
        cancelAction(2),
        onImmediately(3),
        offImmediately(4),
        cycleImmediately(5),
        onByActionTimer(6),
        offByActionTimer(7),
        cycleByActionTimer(8),
        onThenOffByActionTimers(9),
        offThenOnByActionTimers(10)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Set to control the outlet perform action as requested."
        ::= { ipmSlaveDeviceOutletActionEntry 8 }

slaveOutletAction08 OBJECT-TYPE
        SYNTAX INTEGER {
        none(1),
        cancelAction(2),
        onImmediately(3),
        offImmediately(4),
        cycleImmediately(5),
        onByActionTimer(6),
        offByActionTimer(7),
        cycleByActionTimer(8),
        onThenOffByActionTimers(9),
        offThenOnByActionTimers(10)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Set to control the outlet perform action as requested."
        ::= { ipmSlaveDeviceOutletActionEntry 9 }

slaveOutletAction09 OBJECT-TYPE
        SYNTAX INTEGER {
        none(1),
        cancelAction(2),
        onImmediately(3),
        offImmediately(4),
        cycleImmediately(5),
        onByActionTimer(6),
        offByActionTimer(7),
        cycleByActionTimer(8),
        onThenOffByActionTimers(9),
        offThenOnByActionTimers(10)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Set to control the outlet perform action as requested."
        ::= { ipmSlaveDeviceOutletActionEntry 10 }

slaveOutletAction10 OBJECT-TYPE
        SYNTAX INTEGER {
        none(1),
        cancelAction(2),
        onImmediately(3),
        offImmediately(4),
        cycleImmediately(5),
        onByActionTimer(6),
        offByActionTimer(7),
        cycleByActionTimer(8),
        onThenOffByActionTimers(9),
        offThenOnByActionTimers(10)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Set to control the outlet perform action as requested."
        ::= { ipmSlaveDeviceOutletActionEntry 11 }

slaveOutletAction11 OBJECT-TYPE
        SYNTAX INTEGER {
        none(1),
        cancelAction(2),
        onImmediately(3),
        offImmediately(4),
        cycleImmediately(5),
        onByActionTimer(6),
        offByActionTimer(7),
        cycleByActionTimer(8),
        onThenOffByActionTimers(9),
        offThenOnByActionTimers(10)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Set to control the outlet perform action as requested."
        ::= { ipmSlaveDeviceOutletActionEntry 12 }

slaveOutletAction12 OBJECT-TYPE
        SYNTAX INTEGER {
        none(1),
        cancelAction(2),
        onImmediately(3),
        offImmediately(4),
        cycleImmediately(5),
        onByActionTimer(6),
        offByActionTimer(7),
        cycleByActionTimer(8),
        onThenOffByActionTimers(9),
        offThenOnByActionTimers(10)
    }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Set to control the outlet perform action as requested."
        ::= { ipmSlaveDeviceOutletActionEntry 13 }

ipmEnvEmd        OBJECT IDENTIFIER ::= { ipmEnv 1 }      
-- ===========================================================================
--
-- ipmEnvEmd
--
--    Environmental Monitor Device Group
--
-- ===========================================================================

ipmEnvEmdStatus        OBJECT IDENTIFIER ::= { ipmEnvEmd 1 }      
-- ===========================================================================
--
-- ipmEnvEmd
--
--    Environmental Monitor Device Status Group
--
-- ===========================================================================

ipmEnvEmdStatusEmdType OBJECT-TYPE
        SYNTAX  INTEGER {
                unknown(1),
                disabled(2),
                eMD-HT(3),
                eMD-T(4)
                }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "EMD Type."
        ::= { ipmEnvEmdStatus 1 }

ipmEnvEmdStatusTemperature OBJECT-TYPE
        SYNTAX INTEGER (1..10000) --
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "EMD Temperature in 0.1 degree C."
        ::= { ipmEnvEmdStatus  2 }

ipmEnvEmdStatusHumidity OBJECT-TYPE
        SYNTAX INTEGER (1..10000) --
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "EMD Humidity in 0.1%."
        ::= { ipmEnvEmdStatus  3 }

ipmEnvEmdStatusAlarm1 OBJECT-TYPE
        SYNTAX  INTEGER {
                unknown(1),
                disabled(2),
                alarm(3),
                normal(4)
                }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "EMD Alarm-1 state."
        ::= { ipmEnvEmdStatus 4 }

ipmEnvEmdStatusAlarm2 OBJECT-TYPE
        SYNTAX  INTEGER {
                unknown(1),
                disabled(2),
                alarm(3),
                normal(4)
                }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "EMD Alarm-2 state."
        ::= { ipmEnvEmdStatus 5 }

ipmEnvEmdConfig        OBJECT IDENTIFIER ::= { ipmEnvEmd 2 }      
-- ===========================================================================
--
-- ipmEnvEmd
--
--    Environmental Monitor Device Configuration Group
--
-- ===========================================================================
ipmEnvEmdConfigEmdPresence OBJECT-TYPE
        SYNTAX  INTEGER {
                disabled(1),
                autoDetect(2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Configure the EMD presence by auto-detect or not exist (disabled)."
        ::= { ipmEnvEmdConfig 1 }

ipmEnvEmdConfigEmdName OBJECT-TYPE
       SYNTAX DisplayString (SIZE (0..31))
       ACCESS read-write
       STATUS mandatory
       DESCRIPTION
               "The name of Emd."
       ::= { ipmEnvEmdConfig 2 }

ipmEnvEmdConfigTemp        OBJECT IDENTIFIER ::= { ipmEnvEmdConfig 3 }      
-- ===========================================================================
--
-- ipmEnvEmdConfigTemp
--
--    Environmental Monitor Device Temperature Configuration Group
--
-- ===========================================================================
ipmEnvEmdConfigTempName OBJECT-TYPE
       SYNTAX DisplayString (SIZE (0..31))
       ACCESS read-write
       STATUS mandatory
       DESCRIPTION
               "The name of EMD Temperature sensor."
       ::= { ipmEnvEmdConfigTemp 1 }

ipmEnvEmdConfigTempHighSetPoint OBJECT-TYPE
        SYNTAX INTEGER (5..65) --
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "EMD Temperature set point high, alarm will active when temperature 
         over this value, in degree C."
        ::= { ipmEnvEmdConfigTemp  2 }

ipmEnvEmdConfigTempHighStatus OBJECT-TYPE
        SYNTAX  INTEGER {
                enabled(1),
                disabled(2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Enabled/disabled the high setpoint be applied or not"
        ::= { ipmEnvEmdConfigTemp 3 }

ipmEnvEmdConfigTempLowSetPoint OBJECT-TYPE
        SYNTAX INTEGER (5..65) --
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "EMD Temperature set point high, alarm will active when temperature 
         under this value, in degree C."
        ::= { ipmEnvEmdConfigTemp  4 }

ipmEnvEmdConfigTempLowStatus OBJECT-TYPE
        SYNTAX  INTEGER {
                enabled(1),
                disabled(2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Enabled/disabled the low setpoint be applied or not"
        ::= { ipmEnvEmdConfigTemp 5 }

ipmEnvEmdConfigTempOffset OBJECT-TYPE
        SYNTAX  INTEGER {
                t0p0(1),
                t0p5(2),
                t1p0(3),
                t1p5(4),
                t2p0(5),
                t2p5(6),
                t3p0(7),
                t-0p5(8),
                t-1p0(9),
                t-1p5(10),
                t-2p0(11),
                t-2p5(12),
                t-3p0(13)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Offset of temperature in degree C to adjust EMD temperature measurement."
        ::= { ipmEnvEmdConfigTemp 6 }
        
ipmEnvEmdConfigHumi        OBJECT IDENTIFIER ::= { ipmEnvEmdConfig 4 }      
-- ===========================================================================
--
-- ipmEnvEmdConfigHumi
--
--    Environmental Monitor Device Humidity Configuration Group
--
-- ===========================================================================
ipmEnvEmdConfigHumiName OBJECT-TYPE
       SYNTAX DisplayString (SIZE (0..31))
       ACCESS read-write
       STATUS mandatory
       DESCRIPTION
               "The name of EMD Humidity."
       ::= { ipmEnvEmdConfigHumi 1 }

ipmEnvEmdConfigHumiHighSetPoint OBJECT-TYPE
        SYNTAX INTEGER (5..95) --
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "EMD humidity set point high, alarm will active when humidity 
         over this value, in %."
        ::= { ipmEnvEmdConfigHumi  2 }

ipmEnvEmdConfigHumiHighStatus OBJECT-TYPE
        SYNTAX  INTEGER {
                enabled(1),
                disabled(2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Enabled/disabled the high setpoint be applied or not"
        ::= { ipmEnvEmdConfigHumi 3 }

ipmEnvEmdConfigHumiLowSetPoint OBJECT-TYPE
        SYNTAX INTEGER (5..95) --
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "EMD humidity set point low, alarm will active when humidity 
         under this value, in %."
        ::= { ipmEnvEmdConfigHumi  4 }

ipmEnvEmdConfigHumiLowStatus OBJECT-TYPE
        SYNTAX  INTEGER {
                enabled(1),
                disabled(2)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Enabled/disabled the high setpoint be applied or not"
        ::= { ipmEnvEmdConfigHumi 5 }

ipmEnvEmdConfigHumiOffset OBJECT-TYPE
        SYNTAX  INTEGER {
                h0p0(1),
                h1p0(2),
                h2p0(3),
                h3p0(4),
                h4p0(5),
                h5p0(6),
                h6p0(7),
                h-1p0(8),
                h-2p0(9),
                h-3p0(10),
                h-4p0(11),
                h-5p0(12),
                h-6p0(13)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Emd Hum Offset;"
        ::= { ipmEnvEmdConfigHumi 6 }

ipmEnvEmdConfigAlarm1        OBJECT IDENTIFIER ::= { ipmEnvEmdConfig 5 }      
-- ===========================================================================
--
-- ipmEnvEmdConfigAlarm1
--
--    Environmental Monitor Device Alarm-1 Configuration Group
--
-- ===========================================================================
ipmEnvEmdConfigAlarm1Name OBJECT-TYPE
       SYNTAX DisplayString (SIZE (0..31))
       ACCESS read-write
       STATUS mandatory
       DESCRIPTION
               "The name of EMD Alarm-1."
       ::= { ipmEnvEmdConfigAlarm1 1 }

ipmEnvEmdConfigAlarm1Type OBJECT-TYPE
        SYNTAX  INTEGER {
                disabled(1),
                normalOpen(2),
                normalClose(3)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "EMD Alarm-1 type"
        ::= { ipmEnvEmdConfigAlarm1 2 }

ipmEnvEmdConfigAlarm2        OBJECT IDENTIFIER ::= { ipmEnvEmdConfig 6 }      
-- ===========================================================================
--
-- ipmEnvEmdConfigAlarm2
--
--    Environmental Monitor Device Alarm-2 Configuration Group
--
-- ===========================================================================
ipmEnvEmdConfigAlarm2Name OBJECT-TYPE
       SYNTAX DisplayString (SIZE (0..31))
       ACCESS read-write
       STATUS mandatory
       DESCRIPTION
               "The name of EMD Alarm-2."
       ::= { ipmEnvEmdConfigAlarm2 1 }

ipmEnvEmdConfigAlarm2Type OBJECT-TYPE
        SYNTAX  INTEGER {
                disabled(1),
                normalOpen(2),
                normalClose(3)
                }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "EMD Alarm-2 type"
        ::= { ipmEnvEmdConfigAlarm2 2 }


-- ===========================================================================
-- ipmTraps
--
-- iPoManII Trap group
-- ===========================================================================

   -- This section defines the well-known notifications sent by
   -- iPoManII agents.

ipmInletVoltageTooHigh TRAP-TYPE
        ENTERPRISE ipmTraps
        VARIABLES {
    inletConfigIndex,
        inletStatusVoltage,
        inletConfigVoltageHigh,
        inletConfigDesc
        }
        DESCRIPTION
                "CRITICAL: The input voltage over high threshold."
        ::= 1

ipmInletVoltageNotTooHigh TRAP-TYPE
        ENTERPRISE ipmTraps
        VARIABLES {
    inletConfigIndex,
        inletStatusVoltage,
        inletConfigVoltageHigh,
        inletConfigDesc
        }
        DESCRIPTION
                "WARNING: The input voltage return from over high threshold."
        ::= 2

ipmInletVoltageTooLow TRAP-TYPE
        ENTERPRISE ipmTraps
        VARIABLES {
    inletConfigIndex,
        inletStatusVoltage,
        inletConfigVoltageLow,
        inletConfigDesc
        }
        DESCRIPTION
                "CRITICAL: The input voltage under low threshold."
        ::= 3

ipmInletVoltageNotTooLow TRAP-TYPE
        ENTERPRISE ipmTraps
        VARIABLES {
    inletConfigIndex,
        inletStatusVoltage,
        inletConfigVoltageLow,
        inletConfigDesc
        }
        DESCRIPTION
                "WARNING: The input voltage return from under low threshold."
        ::= 4

ipmInletCurrentTooHigh TRAP-TYPE
        ENTERPRISE ipmTraps
        VARIABLES {
    inletConfigIndex,
        inletStatusCurrent,
        inletConfigCurrentHigh,
        inletConfigDesc
        }
        DESCRIPTION
                "CRITICAL: The input current over high threshold."
        ::= 5

ipmInletCurrentNotTooHigh TRAP-TYPE
        ENTERPRISE ipmTraps
        VARIABLES {
    inletConfigIndex,
        inletStatusCurrent,
        inletConfigCurrentHigh,
        inletConfigDesc
        }
        DESCRIPTION
                "WARNING: The input current return from over high threshold."
        ::= 6

ipmInletFrequencyTooHigh TRAP-TYPE
        ENTERPRISE ipmTraps
        VARIABLES {
    inletConfigIndex,
        inletStatusFrequency,
        inletConfigFrequencyHigh,
        inletConfigDesc
        }
        DESCRIPTION
                "CRITICAL: The input frequency over high threshold."
        ::= 7

ipmInletFrequencyNotTooHigh TRAP-TYPE
        ENTERPRISE ipmTraps
        VARIABLES {
    inletConfigIndex,
        inletStatusFrequency,
        inletConfigFrequencyHigh,
        inletConfigDesc
        }
        DESCRIPTION
                "WARNING: The input frequency return from over high threshold."
        ::= 8

ipmInletFrequencyTooLow TRAP-TYPE
        ENTERPRISE ipmTraps
        VARIABLES {
    inletConfigIndex,
        inletStatusFrequency,
        inletConfigFrequencyLow,
        inletConfigDesc
        }
        DESCRIPTION
                "CRITICAL: The input frequency under low threshold."
        ::= 9

ipmInletFrequencyNotTooLow TRAP-TYPE
        ENTERPRISE ipmTraps
        VARIABLES {
    inletConfigIndex,
        inletStatusFrequency,
        inletConfigFrequencyLow,
        inletConfigDesc
        }
        DESCRIPTION
                "WARNING: The input frequency return from under low threshold."
        ::= 10

ipmOutletCurrentTooHigh TRAP-TYPE
        ENTERPRISE ipmTraps
        VARIABLES {
    outletConfigIndex,
        outletStatusCurrent,
        outletConfigCurrentHigh,
        outletConfigDesc
        }
        DESCRIPTION
                "CRITICAL: The output current of outlet over high threshold."
        ::= 11

ipmOutletCurrentNotTooHigh TRAP-TYPE
        ENTERPRISE ipmTraps
        VARIABLES {
    outletConfigIndex,
        outletStatusCurrent,
        outletConfigCurrentHigh,
        outletConfigDesc
        }
        DESCRIPTION
                "WARNING: The output current of outlet return from over high threshold."
        ::= 12

ipmOutletStateChanged TRAP-TYPE
        ENTERPRISE ipmTraps
        VARIABLES {
    outletConfigIndex,
    outletStatusStatus,
        outletConfigDesc
        }
        DESCRIPTION
                "INFORMATION: The outlet state had changed from on to off, or from off to on."
        ::= 13

ipmEmdTemperatureNotHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        VARIABLES {
        ipmEnvEmdStatusTemperature,
        ipmEnvEmdConfigTempHighSetPoint,
        ipmEnvEmdConfigTempName
        }
        DESCRIPTION
                "INFORMATION: emd Temperature Not High."
        ::= 14

ipmEmdTemperatureTooHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        VARIABLES {
        ipmEnvEmdStatusTemperature,
        ipmEnvEmdConfigTempHighSetPoint,
        ipmEnvEmdConfigTempName
        }
        DESCRIPTION
                "WARNING:  emd Temperature Too High."
        ::= 15

ipmEmdTemperatureNotLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        VARIABLES {
        ipmEnvEmdStatusTemperature,
        ipmEnvEmdConfigTempLowSetPoint,
        ipmEnvEmdConfigTempName
        }
        DESCRIPTION
                "INFORMATION: emd Temperature Not Low."
        ::= 16

ipmEmdTemperatureTooLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        VARIABLES {
        ipmEnvEmdStatusTemperature,
        ipmEnvEmdConfigTempLowSetPoint,
        ipmEnvEmdConfigTempName
        }
        DESCRIPTION
                "WARNING: emd Temperature Too Low."
        ::= 17

ipmEmdHumidityNotHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        VARIABLES {
        ipmEnvEmdStatusHumidity,
        ipmEnvEmdConfigHumiHighSetPoint,
        ipmEnvEmdConfigHumiName
        }
        DESCRIPTION
                "INFORMATION: emd Humidity Not High."
        ::= 18

ipmEmdHumidityTooHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        VARIABLES {
        ipmEnvEmdStatusHumidity,
        ipmEnvEmdConfigHumiHighSetPoint,
        ipmEnvEmdConfigHumiName
        }
        DESCRIPTION
                "WARNING: emd Humidity Too High."
        ::= 19

ipmEmdHumidityNotLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        VARIABLES {
        ipmEnvEmdStatusHumidity,
        ipmEnvEmdConfigHumiLowSetPoint,
        ipmEnvEmdConfigHumiName
        }
        DESCRIPTION
                "INFORMATION: emd Humidity Not Low."
        ::= 20

ipmEmdHumidityTooLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        VARIABLES {
        ipmEnvEmdStatusHumidity,
        ipmEnvEmdConfigHumiLowSetPoint,
        ipmEnvEmdConfigHumiName
        }
        DESCRIPTION
                "WARNING: emd Humidity Too Low."
        ::= 21

ipmEmdAlarm1Normal TRAP-TYPE
        ENTERPRISE      ipmTraps
        VARIABLES {
        ipmEnvEmdConfigAlarm1Type,
        ipmEnvEmdConfigAlarm1Name
        }
        DESCRIPTION
                "INFORMATION: emd Alarm1 Normal."
        ::= 22

ipmEmdAlarm1Active TRAP-TYPE
        ENTERPRISE      ipmTraps
        VARIABLES {
        ipmEnvEmdConfigAlarm1Type,
        ipmEnvEmdConfigAlarm1Name
        }
        DESCRIPTION
                "WARNING: emd Alarm1 Active."
        ::= 23
        
ipmEmdAlarm2Normal TRAP-TYPE
        ENTERPRISE      ipmTraps
        VARIABLES {
        ipmEnvEmdConfigAlarm2Type,
        ipmEnvEmdConfigAlarm2Name
        }
        DESCRIPTION
                "INFORMATION: emd Alarm2 Normal."
        ::= 24

ipmEmdAlarm2Active TRAP-TYPE
        ENTERPRISE      ipmTraps
        VARIABLES {
        ipmEnvEmdConfigAlarm2Type,
        ipmEnvEmdConfigAlarm2Name
        }
        DESCRIPTION
                "WARNING: emd Alarm2 Active."
        ::= 25

ipmSlave01Inlet01OverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave01 input01 voltage over high threshold."
        ::= 26

ipmSlave01Inlet01NotOverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave01 input01 voltage Not over high threshold."
        ::= 27

ipmSlave01Inlet02OverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave01 input02 voltage over high threshold."
        ::= 28

ipmSlave01Inlet02NotOverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave01 input02 voltage Not over high threshold."
        ::= 29

ipmSlave01Inlet01UnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave01 input01 voltage under low threshold."
        ::= 30

ipmSlave01Inlet01NotUnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave01 input01 voltage Not under low threshold."
        ::= 31

ipmSlave01Inlet02UnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave01 input02 voltage under low threshold."
        ::= 32

ipmSlave01Inlet02NotUnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave01 input02 voltage Not under low threshold."
        ::= 33

ipmSlave01Inlet01CurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave01 input01 current over high threshold."
        ::= 34

ipmSlave01Inlet01NotCurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave01 input01 current not over high threshold."
        ::= 35

ipmSlave01Inlet02CurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave01 input02 current over high threshold."
        ::= 36

ipmSlave01Inlet02NotCurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave01 input02 current not over high threshold."
        ::= 37

ipmSlave01EmdTemperatureNotHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave01 emd Temperature Not High."
        ::= 38

ipmSlave01EmdTemperatureTooHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave01 emd Temperature Too High."
        ::= 39

ipmSlave01EmdTemperatureNotLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave01 emd Temperature Not Low."
        ::= 40

ipmSlave01EmdTemperatureTooLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave01 emd Temperature Too Low."
        ::= 41

ipmSlave01EmdHumidityNotHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave01 emd Humidity Not High."
        ::= 42

ipmSlave01EmdHumidityTooHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave01 emd Humidity Too High."
        ::= 43

ipmSlave01EmdHumidityNotLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave01 emd Humidity Not Low."
        ::= 44

ipmSlave01EmdHumidityTooLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave01 emd Humidity Too Low."
        ::= 45

ipmSlave01EmdAlarm1Normal TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave01 emd Alarm1 Normal."
        ::= 46

ipmSlave01EmdAlarm1Active TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave01 emd Alarm1 Active."
        ::= 47
        
ipmSlave01EmdAlarm2Normal TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave01 emd Alarm2 Normal."
        ::= 48

ipmSlave01EmdAlarm2Active TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave01 emd Alarm2 Active."
        ::= 49

ipmSlave01OutletCurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave01 Outlet Current over threshold."
        ::= 50

ipmSlave02Inlet01OverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave02 input01 voltage over high threshold."
        ::= 51

ipmSlave02Inlet01NotOverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave02 input01 voltage Not over high threshold."
        ::= 52

ipmSlave02Inlet02OverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave02 input02 voltage over high threshold."
        ::= 53

ipmSlave02Inlet02NotOverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave02 input02 voltage Not over high threshold."
        ::= 54

ipmSlave02Inlet01UnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave02 input01 voltage under low threshold."
        ::= 55

ipmSlave02Inlet01NotUnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave02 input01 voltage Not under low threshold."
        ::= 56

ipmSlave02Inlet02UnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave02 input02 voltage under low threshold."
        ::= 57

ipmSlave02Inlet02NotUnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave02 input02 voltage Not under low threshold."
        ::= 58

ipmSlave02Inlet01CurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave02 input01 current over high threshold."
        ::= 59

ipmSlave02Inlet01NotCurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave02 input01 current not over high threshold."
        ::= 60

ipmSlave02Inlet02CurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave02 input02 current over high threshold."
        ::= 61

ipmSlave02Inlet02NotCurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave02 input02 current not over high threshold."
        ::= 62

ipmSlave02EmdTemperatureNotHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave02 emd Temperature Not High."
        ::= 63

ipmSlave02EmdTemperatureTooHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave02 emd Temperature Too High."
        ::= 64

ipmSlave02EmdTemperatureNotLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave02 emd Temperature Not Low."
        ::= 65

ipmSlave02EmdTemperatureTooLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave02 emd Temperature Too Low."
        ::= 66

ipmSlave02EmdHumidityNotHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave02 emd Humidity Not High."
        ::= 67

ipmSlave02EmdHumidityTooHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave02 emd Humidity Too High."
        ::= 68

ipmSlave02EmdHumidityNotLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave02 emd Humidity Not Low."
        ::= 69

ipmSlave02EmdHumidityTooLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave02 emd Humidity Too Low."
        ::= 70

ipmSlave02EmdAlarm1Normal TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave02 emd Alarm1 Normal."
        ::= 71

ipmSlave02EmdAlarm1Active TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave02 emd Alarm1 Active."
        ::= 72
        
ipmSlave02EmdAlarm2Normal TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave02 emd Alarm2 Normal."
        ::= 73

ipmSlave02EmdAlarm2Active TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave02 emd Alarm2 Active."
        ::= 74

ipmSlave02OutletCurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave02 Outlet Current over threshold."
        ::= 75

ipmSlave03Inlet01OverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave03 input01 voltage over high threshold."
        ::= 76

ipmSlave03Inlet01NotOverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave03 input01 voltage Not over high threshold."
        ::= 77

ipmSlave03Inlet02OverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave03 input02 voltage over high threshold."
        ::= 78

ipmSlave03Inlet02NotOverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave03 input02 voltage Not over high threshold."
        ::= 79

ipmSlave03Inlet01UnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave03 input01 voltage under low threshold."
        ::= 80

ipmSlave03Inlet01NotUnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave03 input01 voltage Not under low threshold."
        ::= 81

ipmSlave03Inlet02UnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave03 input02 voltage under low threshold."
        ::= 82

ipmSlave03Inlet02NotUnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave03 input02 voltage Not under low threshold."
        ::= 83

ipmSlave03Inlet01CurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave03 input01 current over high threshold."
        ::= 84

ipmSlave03Inlet01NotCurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave03 input01 current not over high threshold."
        ::= 85

ipmSlave03Inlet02CurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave03 input02 current over high threshold."
        ::= 86

ipmSlave03Inlet02NotCurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave03 input02 current not over high threshold."
        ::= 87

ipmSlave03EmdTemperatureNotHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave03 emd Temperature Not High."
        ::= 88

ipmSlave03EmdTemperatureTooHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave03 emd Temperature Too High."
        ::= 89

ipmSlave03EmdTemperatureNotLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave03 emd Temperature Not Low."
        ::= 90

ipmSlave03EmdTemperatureTooLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave03 emd Temperature Too Low."
        ::= 91

ipmSlave03EmdHumidityNotHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave03 emd Humidity Not High."
        ::= 92

ipmSlave03EmdHumidityTooHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave03 emd Humidity Too High."
        ::= 93

ipmSlave03EmdHumidityNotLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave03 emd Humidity Not Low."
        ::= 94

ipmSlave03EmdHumidityTooLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave03 emd Humidity Too Low."
        ::= 95

ipmSlave03EmdAlarm1Normal TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave03 emd Alarm1 Normal."
        ::= 96

ipmSlave03EmdAlarm1Active TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave03 emd Alarm1 Active."
        ::= 97
        
ipmSlave03EmdAlarm2Normal TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave03 emd Alarm2 Normal."
        ::= 98

ipmSlave03EmdAlarm2Active TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave03 emd Alarm2 Active."
        ::= 99

ipmSlave03OutletCurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave03 Outlet Current over threshold."
        ::= 100

ipmSlave04Inlet01OverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave04 input01 voltage over high threshold."
        ::= 101

ipmSlave04Inlet01NotOverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave04 input01 voltage Not over high threshold."
        ::= 102

ipmSlave04Inlet02OverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave04 input02 voltage over high threshold."
        ::= 103

ipmSlave04Inlet02NotOverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave04 input02 voltage Not over high threshold."
        ::= 104

ipmSlave04Inlet01UnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave04 input01 voltage under low threshold."
        ::= 105

ipmSlave04Inlet01NotUnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave04 input01 voltage Not under low threshold."
        ::= 106

ipmSlave04Inlet02UnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave04 input02 voltage under low threshold."
        ::= 107

ipmSlave04Inlet02NotUnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave04 input02 voltage Not under low threshold."
        ::= 108

ipmSlave04Inlet01CurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave04 input01 current over high threshold."
        ::= 109

ipmSlave04Inlet01NotCurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave04 input01 current not over high threshold."
        ::= 110

ipmSlave04Inlet02CurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave04 input02 current over high threshold."
        ::= 111

ipmSlave04Inlet02NotCurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave04 input02 current not over high threshold."
        ::= 112

ipmSlave04EmdTemperatureNotHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave04 emd Temperature Not High."
        ::= 113

ipmSlave04EmdTemperatureTooHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave04 emd Temperature Too High."
        ::= 114

ipmSlave04EmdTemperatureNotLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave04 emd Temperature Not Low."
        ::= 115

ipmSlave04EmdTemperatureTooLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave04 emd Temperature Too Low."
        ::= 116

ipmSlave04EmdHumidityNotHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave04 emd Humidity Not High."
        ::= 117

ipmSlave04EmdHumidityTooHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave04 emd Humidity Too High."
        ::= 118

ipmSlave04EmdHumidityNotLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave04 emd Humidity Not Low."
        ::= 119

ipmSlave04EmdHumidityTooLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave04 emd Humidity Too Low."
        ::= 120

ipmSlave04EmdAlarm1Normal TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave04 emd Alarm1 Normal."
        ::= 121

ipmSlave04EmdAlarm1Active TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave04 emd Alarm1 Active."
        ::= 122
        
ipmSlave04EmdAlarm2Normal TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave04 emd Alarm2 Normal."
        ::= 123

ipmSlave04EmdAlarm2Active TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave04 emd Alarm2 Active."
        ::= 124

ipmSlave04OutletCurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave04 Outlet Current over threshold."
        ::= 125

ipmSlave05Inlet01OverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave05 input01 voltage over high threshold."
        ::= 126

ipmSlave05Inlet01NotOverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave05 input01 voltage Not over high threshold."
        ::= 127

ipmSlave05Inlet02OverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave05 input02 voltage over high threshold."
        ::= 128

ipmSlave05Inlet02NotOverHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave05 input02 voltage Not over high threshold."
        ::= 129

ipmSlave05Inlet01UnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave05 input01 voltage under low threshold."
        ::= 130

ipmSlave05Inlet01NotUnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave05 input01 voltage Not under low threshold."
        ::= 131

ipmSlave05Inlet02UnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave05 input02 voltage under low threshold."
        ::= 132

ipmSlave05Inlet02NotUnderLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave05 input02 voltage Not under low threshold."
        ::= 133

ipmSlave05Inlet01CurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave05 input01 current over high threshold."
        ::= 134

ipmSlave05Inlet01NotCurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave05 input01 current not over high threshold."
        ::= 135

ipmSlave05Inlet02CurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave05 input02 current over high threshold."
        ::= 136

ipmSlave05Inlet02NotCurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "CRITICAL: The Slave05 input02 current not over high threshold."
        ::= 137

ipmSlave05EmdTemperatureNotHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave05 emd Temperature Not High."
        ::= 138

ipmSlave05EmdTemperatureTooHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave05 emd Temperature Too High."
        ::= 139

ipmSlave05EmdTemperatureNotLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave05 emd Temperature Not Low."
        ::= 140

ipmSlave05EmdTemperatureTooLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave05 emd Temperature Too Low."
        ::= 141

ipmSlave05EmdHumidityNotHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave05 emd Humidity Not High."
        ::= 142

ipmSlave05EmdHumidityTooHigh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave05 emd Humidity Too High."
        ::= 143

ipmSlave05EmdHumidityNotLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave05 emd Humidity Not Low."
        ::= 144

ipmSlave05EmdHumidityTooLow TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave05 emd Humidity Too Low."
        ::= 145

ipmSlave05EmdAlarm1Normal TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave05 emd Alarm1 Normal."
        ::= 146

ipmSlave05EmdAlarm1Active TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave05 emd Alarm1 Active."
        ::= 147
        
ipmSlave05EmdAlarm2Normal TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "INFORMATION: The Slave05 emd Alarm2 Normal."
        ::= 148

ipmSlave05EmdAlarm2Active TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave05 emd Alarm2 Active."
        ::= 149

ipmSlave05OutletCurrentOverTh TRAP-TYPE
        ENTERPRISE      ipmTraps
        DESCRIPTION
                "WARNING: The Slave05 Outlet Current over threshold."
        ::= 150

   END