--PPC-MIB { iso(1) org(3) dod(6) internet(1) private(4)
-- enterprises(1) ppc(935) }
-- Title: PPC TOP LEVEL MIB
-- Date: January 07, 1994    Version 1.00
--
-- Date: January 17, 1994    Version 1.01
--
-- Date: July 14, 1994    Version 1.02
--
-- Date: May 16, 2003    Version 2.00

XPPC-MIB DEFINITIONS ::= BEGIN

IMPORTS
        TRAP-TYPE
                FROM RFC-1215
        DisplayString
                FROM RFC1213-MIB
        OBJECT-TYPE
                FROM RFC-1212
        enterprises,
        IpAddress
                FROM RFC1155-SMI;


ppc OBJECT IDENTIFIER 
   ::= { enterprises 935 }

products OBJECT IDENTIFIER 
   ::= { ppc 1 }

ppcmgmt OBJECT IDENTIFIER 
   ::= { ppc 2 }

hardware OBJECT IDENTIFIER 
   ::= { products 1 }

mconfig OBJECT IDENTIFIER 
   ::= { ppcmgmt 1 }

ups OBJECT IDENTIFIER 
   ::= { hardware 1 }

upsIdentp OBJECT IDENTIFIER 
   ::= { ups 1 }

upsBatteryp OBJECT IDENTIFIER 
   ::= { ups 2 }

upsInputp OBJECT IDENTIFIER 
   ::= { ups 3 }

upsOutputp OBJECT IDENTIFIER 
   ::= { ups 4 }

upsConfigp OBJECT IDENTIFIER 
   ::= { ups 5 }

upsControlp OBJECT IDENTIFIER 
   ::= { ups 6 }

upsTestp OBJECT IDENTIFIER 
   ::= { ups 7 }

upsThreePhase OBJECT IDENTIFIER 
   ::= { ups 8 }

upsEnvironment OBJECT IDENTIFIER 
   ::= { ups 9 }

upsBaseIdent OBJECT IDENTIFIER 
   ::= { upsIdentp 1 }

upsSmartIdent OBJECT IDENTIFIER 
   ::= { upsIdentp 2 }

upsBaseBattery OBJECT IDENTIFIER 
   ::= { upsBatteryp 1 }

upsSmartBattery OBJECT IDENTIFIER 
   ::= { upsBatteryp 2 }

upsBaseInput OBJECT IDENTIFIER 
   ::= { upsInputp 1 }

upsSmartInput OBJECT IDENTIFIER 
   ::= { upsInputp 2 }

upsBaseOutput OBJECT IDENTIFIER 
   ::= { upsOutputp 1 }

upsSmartOutput OBJECT IDENTIFIER 
   ::= { upsOutputp 2 }

upsBaseConfig OBJECT IDENTIFIER 
   ::= { upsConfigp 1 }

upsSmartConfig OBJECT IDENTIFIER 
   ::= { upsConfigp 2 }

upsBaseControl OBJECT IDENTIFIER 
   ::= { upsControlp 1 }

upsSmartControl OBJECT IDENTIFIER 
   ::= { upsControlp 2 }

upsBaseTest OBJECT IDENTIFIER 
   ::= { upsTestp 1 }

upsSmartTest OBJECT IDENTIFIER 
   ::= { upsTestp 2 }

upsThreePhaseBatteryGrp OBJECT IDENTIFIER 
   ::= { upsThreePhase 1 }

upsThreePhaseInputGrp OBJECT IDENTIFIER 
   ::= { upsThreePhase 2 }

upsThreePhaseOutputGrp OBJECT IDENTIFIER 
   ::= { upsThreePhase 3 }

upsThreePhaseBypassGrp OBJECT IDENTIFIER 
   ::= { upsThreePhase 4 }

upsThreePhaseDCandRectifierStatusGrp OBJECT IDENTIFIER 
   ::= { upsThreePhase 5 }

upsThreePhaseUPSStatusGrp OBJECT IDENTIFIER 
   ::= { upsThreePhase 6 }

upsThreePhaseFaultStatusGrp OBJECT IDENTIFIER 
   ::= { upsThreePhase 7 }

upsThreePhaseRatingGrp OBJECT IDENTIFIER 
   ::= { upsThreePhase 8 }

-- object types
-- the ppcmgmt group
-- the mconfig group

mconfigTrapsReceiversNum OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The number of managers to send traps to."
   ::= { mconfig 1 }


mconfigTrapsReceiversTable OBJECT-TYPE
        SYNTAX SEQUENCE OF MconfigTrapsReceiversEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of managers to send traps to.  The number of
                entries is given by the value of mconfigNumTrapReceivers"
   ::= { mconfig 2 }


mconfigTrapsReceiversEntry OBJECT-TYPE
        SYNTAX MconfigTrapsReceiversEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The managers to send traps to."
        INDEX {
                trapsIndex }
   ::= { mconfigTrapsReceiversTable 1 }


MconfigTrapsReceiversEntry ::= SEQUENCE {
        trapsIndex              INTEGER,
        trapsReceiverAddr       IpAddress,
        receiverCommunityString DisplayString,
        severityLevel           INTEGER,
        receiverAccept          INTEGER }


trapsIndex OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index to a trap receiver entry."
   ::= { mconfigTrapsReceiversEntry 1 }


trapsReceiverAddr OBJECT-TYPE
        SYNTAX IpAddress
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The IP address of the manager to send a trap to."
   ::= { mconfigTrapsReceiversEntry 2 }


receiverCommunityString OBJECT-TYPE
        SYNTAX DisplayString
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The community name to use in the trap when
                sent to the manager."
   ::= { mconfigTrapsReceiversEntry 3 }


severityLevel OBJECT-TYPE
        SYNTAX INTEGER {
                        information(1),
                        warning(2),
                        severe(3) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The severity threshold of traps to send to the manager.
                traps are labeled in severity as informational(1), warning(2),
                severe(3).  Only traps of equal or greater severity than
                this value are sent to the manager."
   ::= { mconfigTrapsReceiversEntry 4 }


receiverAccept OBJECT-TYPE
        SYNTAX INTEGER {
                        yes(1),
                        no(2) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "An entry will become active if yes, and will
                be deleted if no."
   ::= { mconfigTrapsReceiversEntry 5 }


-- the ups group
-- the upsBaseIdent group

upsBaseIdentModel OBJECT-TYPE
        SYNTAX DisplayString
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The UPS model name (e.g. 'Intelligent 8000E 900VA')."
   ::= { upsBaseIdent 1 }


upsBaseIdentUpsName OBJECT-TYPE
        SYNTAX DisplayString
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "An 8 byte ID string identifying the UPS.  This object
                can be set by the administrator."
   ::= { upsBaseIdent 2 }


-- the upsSmartIdent group

upsSmartIdentFirmwareRevision OBJECT-TYPE
        SYNTAX DisplayString
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The firmware revision of the UPS system."
   ::= { upsSmartIdent 1 }


upsSmartIdentDateOfManufacture OBJECT-TYPE
        SYNTAX DisplayString
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The date when the UPS was manufactured in mm/dd/yy format."
   ::= { upsSmartIdent 2 }


upsSmartIdentUpsSerialNumber OBJECT-TYPE
        SYNTAX DisplayString
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "An 8-character string identifying the serial number of
                the UPS internal microprocessor.  This number is set at
                the factory.  NOTE: This number does NOT correspond to
                the serial number on the rear of the UPS."
   ::= { upsSmartIdent 3 }


upsSmartIdentAgentFirmwareRevision OBJECT-TYPE
        SYNTAX DisplayString
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The firmware revision of the UPS SNMP Proxy agent."
   ::= { upsSmartIdent 4 }


-- the upsBaseBattery group

upsBaseBatteryStatus OBJECT-TYPE
        SYNTAX INTEGER {
                        unknown(1),
                        batteryNormal(2),
                        batteryLow(3) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The status of the UPS batteries.  A batteryLow(3)
                value indicates the UPS will be unable to sustain the
                current load, and its services will be lost if power is
                not restored.  The amount of run time in reserve at the
                time of low battery can be configured by the
                upsSmartConfigLowBatteryRunTime."
   ::= { upsBaseBattery 1 }


upsBaseBatteryTimeOnBattery OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The elapsed time in seconds since the UPS has switched
                to battery power."
   ::= { upsBaseBattery 2 }


upsBaseBatteryLastReplaceDate OBJECT-TYPE
        SYNTAX DisplayString
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The date when the UPS system's batteries were last replaced
                in mm/dd/yy format.   For UPS models, this value is originally
                set in the factory.  When the UPS batteries are replaced,
                this value should be reset by the administrator."
   ::= { upsBaseBattery 3 }


-- the upsSmartBattery group

upsSmartBatteryCapacity OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The remaining battery capacity expressed in
                percent of full capacity."
   ::= { upsSmartBattery 1 }


upsSmartBatteryVoltage OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The current battery voltage expressed in 1/10 VDC."
   ::= { upsSmartBattery 2 }


upsSmartBatteryTemperature OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The current internal UPS temperature expressed in tenths of
                a Celsius degree."
   ::= { upsSmartBattery 3 }


upsSmartBatteryRunTimeRemaining OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The UPS battery run time remaining before battery
                exhaustion, in seconds."
   ::= { upsSmartBattery 4 }


upsSmartBatteryReplaceIndicator OBJECT-TYPE
        SYNTAX INTEGER {
                        noBatteryNeedsReplacing(1),
                        batteryNeedsReplacing(2) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Indicates whether the UPS batteries need replacing."
   ::= { upsSmartBattery 5 }


upsSmartBatteryFullChargeVoltage OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The fully charged battery voltage of the battery system
                used in the UPS, expressed in tenths of a volt."
   ::= { upsSmartBattery 6 }


upsSmartBatteryCurrent OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The current battery current expressed in percent of
                maximum current."
   ::= { upsSmartBattery 7 }


-- the upsBaseInput group

upsBaseInputPhase OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The current AC input phase."
   ::= { upsBaseInput 1 }


-- the upsSmartInput group

upsSmartInputLineVoltage OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The current utility line voltage in 1/10 VAC."
   ::= { upsSmartInput 1 }


upsSmartInputMaxLineVoltage OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The maximum utility line voltage in 1/10 VAC over the
                previous 1 minute period."
   ::= { upsSmartInput 2 }


upsSmartInputMinLineVoltage OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The minimum utility line voltage in 1/10 VAC over the
                previous 1 minute period."
   ::= { upsSmartInput 3 }


upsSmartInputFrequency OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The current input frequency to the UPS system in 1/10 Hz."
   ::= { upsSmartInput 4 }


upsSmartInputLineFailCause OBJECT-TYPE
        SYNTAX INTEGER {
                        noTransfer(1),
                        highLineVoltage(2),
                        brownout(3),
                        blackout(4),
                        smallMomentarySag(5),
                        deepMomentarySag(6),
                        smallMomentarySpike(7),
                        largeMomentarySpike(8) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The reason for the occurrence of the last transfer
                to UPS battery power.  The variable is set to
                noTransfer(1) if there is no transfer yet.   The variable
                is set to highLineVoltage(2) if the transfer to battery is
                caused by an over voltage greater than the high transfer
                voltage. The variable is set to brownout(3) if the duration
                of the outage is greater than five seconds and the line
                voltage is between 40 percent of the rated output voltage and
                the low transfer voltage. The variable is set to blackout(4)
                if the duration of the outage is greater than five seconds and
                the line voltage is between 40 percent of the rated output voltage
                and ground.  The variable is set to smallMomentarySag(5)
                if the duration of the outage is less than five seconds and
                the line voltage is between 40 percent of the rated output voltage
                and the low transfer voltage.  The variable is set to
                deepMomentarySag(6) if the duration of the outage is less
                than five seconds and the line voltage is between 40 percent of the
                rated output voltage and ground."
   ::= { upsSmartInput 5 }


-- the upsBaseOutput group

upsBaseOutputStatus OBJECT-TYPE
        SYNTAX INTEGER {
                        unknown(1),
                        onLine(2),
                        onBattery(3),
                        onBoost(4),
                        sleeping(5),
                        onBypass(6),
                        rebooting(7),
                        standBy(8),
                        onBuck(9) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The current state of the UPS.  If the UPS is unable
                to determine the state of the UPS this variable is set
                to unknown(1)."
   ::= { upsBaseOutput 1 }


upsBaseOutputPhase OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The current output phase."
   ::= { upsBaseOutput 2 }


-- the upsSmartOutput group

upsSmartOutputVoltage OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The output voltage of the UPS system in 1/10 VAC."
   ::= { upsSmartOutput 1 }


upsSmartOutputFrequency OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The current output frequency of the UPS system in 1/10 Hz."
   ::= { upsSmartOutput 2 }


upsSmartOutputLoad OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The current UPS load expressed in percent
                of rated capacity."
   ::= { upsSmartOutput 3 }


-- the upsBaseConfig group

upsBaseConfigNumDevices OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The number of devices that are plugged into the UPS."
   ::= { upsBaseConfig 1 }


upsBaseConfigDeviceTable OBJECT-TYPE
        SYNTAX SEQUENCE OF UpsBaseConfigDeviceEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "A list of devices that are plugged into the UPS.  The
                number of entries is given by the value of
                upsBaseConfigNumDevices."
   ::= { upsBaseConfig 2 }


upsBaseConfigDeviceEntry OBJECT-TYPE
        SYNTAX UpsBaseConfigDeviceEntry
        ACCESS not-accessible
        STATUS mandatory
        DESCRIPTION
                "The devices plugged in to the UPS."
        INDEX {
                indexOfDevice }
   ::= { upsBaseConfigDeviceTable 1 }


UpsBaseConfigDeviceEntry ::= SEQUENCE {
        indexOfDevice    INTEGER,
        nameOfDevice     DisplayString,
        vaRatingOfDevice INTEGER,
        deviceAccept     INTEGER }


indexOfDevice OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The index of the device that is plugged into the UPS."
   ::= { upsBaseConfigDeviceEntry 1 }


nameOfDevice OBJECT-TYPE
        SYNTAX DisplayString
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The name/description of the device plugged into the UPS."
   ::= { upsBaseConfigDeviceEntry 2 }


vaRatingOfDevice OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The volt-amp rating of the device plugged into the UPS."
   ::= { upsBaseConfigDeviceEntry 3 }


deviceAccept OBJECT-TYPE
        SYNTAX INTEGER {
                        yes(1),
                        no(2) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "An entry is added if yes, the entry is deleted if no."
   ::= { upsBaseConfigDeviceEntry 4 }


-- the upsSmartConfig group

upsSmartConfigRatedOutputVoltage OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The nominal output voltage from the UPS in 1/10 VAC.
                Possible values are 1000, 1200, 2080, 2200, 2250, 2300
                and 2400.
                                
                NOTE: Only units that are 2200, 2250, 2300 and 2400 can
                be changed.  Allowable values are 2200, 2250, 2300 and
                2400.
                                
                For these adjustable units, if a value other than
                a supported value is provided in a set request, the
                UPS interprets it as the next lower acceptable value.
                If the provided value is lower than the lowest acceptable
                value, the lowest acceptable value is used."
   ::= { upsSmartConfig 1 }


upsSmartConfigHighTransferVolt OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The maximum line voltage in 1/10 VAC allowed before the
                UPS system transfers to battery backup.
                                
                Allowed value depend on the UPS used:
                120 Volt units allow settings of 1290, 1320, 1350, 1380.
                100 Volt units allow settings of 1080, 1100, 1120, 1140.
                230 Volt units allow settings of 2530, 2640, 2710, 2800.
                208 Volt units allow settings of 2240, 2290, 2340, 2390.
                                
                If a value other than a supported value is provided in a
                set request, the UPS interprets it as the next lower
                acceptable value.  If the provided value is lower than
                the lowest acceptable value, the lowest acceptable
                value is used."
   ::= { upsSmartConfig 2 }


upsSmartConfigLowTransferVolt OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The minimum line voltage in 1/10 VAC allowed before the
                UPS system transfers to battery backup.
                                
                Allowable values depend on the UPS used:
                120 Volt units allow settings of  970, 1000, 1030, 1060.
                100 Volt units allow settings of 810, 830, 850, 870.
                230 Volt units allow settings of 1880, 1960, 2040, 2080.
                208 Volt units allow settings of 1680, 1720, 1770, 1820.
                                
                If a value other than a supported value is provided in a
                set request, the UPS interprets it as a the next higher
                acceptable value.  If the provided value is higher than
                the highest acceptable value, the highest acceptable
                value is used."
   ::= { upsSmartConfig 3 }


upsSmartConfigAlarm OBJECT-TYPE
        SYNTAX INTEGER {
                        timed(1),
                        atLowBattery(2),
                        never(3) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "A flag indicating how the UPS should handle audible line fail
                alarms."
   ::= { upsSmartConfig 4 }


upsSmartConfigAlarmTimer OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The time in seconds after initial line failure at which the
                UPS begins emitting audible alarms (beeping).  This timer is
                observerd only if the value of extControlAlarm is timed(2).
                Allowed values are 0 or 30 seconds.
                                
                If a value other than a supported value is provided in a
                set request, the UPS interprets it as a the next lower
                acceptable value.  If the provided value is lower than
                the lowest acceptable value, the lowest acceptable
                value is used."
   ::= { upsSmartConfig 5 }


upsSmartConfigMinReturnCapacity OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The minimum battery capacity as a percent of full capacity
                required before the UPS will return from a low battery
                shutdown condition.  In other words, the UPS will not
                re-energize the output until the battery capacity is equal
                to this value. Allowed values are 0, 10, 25, or 90  percent.
                                
                If a value other than a supported value is provided in a
                set request, the UPS interprets it as a the next higher
                acceptable value.  If the provided value is higher than
                the highest acceptable value, the highest acceptable
                value is used."
   ::= { upsSmartConfig 6 }


upsSmartConfigSensitivity OBJECT-TYPE
        SYNTAX INTEGER {
                        auto(1),
                        low(2),
                        medium(3),
                        high(4) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The sensitivity of the UPS to utility line abnormalities
                or noises."
   ::= { upsSmartConfig 7 }


upsSmartConfigLowBatteryRunTime OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The desired run time in seconds once the low battery
                condition is reached.  Allowed values are 120, 300, 420,
                or 600 seconds.  During this time the UPS will produce a
                constant warning tone which can not be disabled.
                                
                If a value other than a supported value is provided in a
                set request, the UPS interprets it as a the next higher
                acceptable value.  If the provided value is higher than
                the highest acceptable value, the highest acceptable
                value is used."
   ::= { upsSmartConfig 8 }


upsSmartConfigReturnDelay OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay in seconds after utility line power returns
                before the UPS will turn on.  This value is also used
                when the UPS comes out of a reboot and before the UPS
                wakes up from 'sleep' mode.  Allowed values are 0, 60,
                180 and 300 seconds.
                                
                If a value other than a supported value is provided in a
                set request, the UPS interprets it as a the next higher
                acceptable value.  If the provided value is higher than
                the highest acceptable value, the highest acceptable
                value is used."
   ::= { upsSmartConfig 9 }


upsSmartConfigShutoffDelay OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The delay in seconds the UPS remains on after being told
                to turn off.  Allowed values are 12, 18, 24, 30, 36, 42,
                48, 54, 60, 120, 180, 240, 300, 360, 420, 480, 540, and
                600 seconds.
                                
                If a value other than a supported value is provided in a
                set request, the UPS interprets it as next higher acceptable
                value.  If the provided value is higher than the highest
                acceptable value, the highest acceptable value is used."
   ::= { upsSmartConfig 10 }


upsSmartConfigUpsSleepTime OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The time in minutes for the UPS to go to 'sleep' when
                instructed.  When in sleep mode, the UPS will not provide
                output power regardless of the input line state.  Once the
                specified time has elapsed, output power will be restored.
                                
                This is a configuration setting.  The UPS will not go to
                sleep until told to do so by the manager from a management
                station.
                                
                Any input value is allowed, however the UPS only recognizes
                0 - 9999 minutes in one minute increments.
                                
                If the provided value is higher than the highest acceptable
                value, the highest acceptable value is used."
   ::= { upsSmartConfig 11 }


upsSmartConfigSetEEPROMDefaults OBJECT-TYPE
        SYNTAX INTEGER {
                        noSetEEPROMDefaults(1),
                        setEEPROMDefaults(2) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "WRITE: Resets the UPS EEPROM variables to default values.
                READ: returns 0"
   ::= { upsSmartConfig 12 }


-- the upsBaseControl group

upsBaseControlConserveBattery OBJECT-TYPE
        SYNTAX INTEGER {
                        noTurnOffUps(1),
                        turnUpsOffToConserveBattery(2),
                        turnUpsOffToConserveBatteryDelay(3) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Setting this variable to turnUpsOffToConserveBattery(2)
                causes a UPS on battery to be put into 'sleep' mode immediately.
                The (10) means suspending time(10 minutes) before turn off UPS.
                UPS will turn back on when utility power is restored.
                Attempting to turn off a UPS that is not on battery will
                result in a badValue error.
                                
                Setting this value to noTurnOffUps(1) has no
                effect.
                                
                The value noTurnOffUps(1) will always be returned
                when the variable is read."
   ::= { upsBaseControl 1 }


-- the upsSmartControl group

upsSmartControlUpsOff OBJECT-TYPE
        SYNTAX INTEGER {
                        noTurnUpsOff(1),
                        turnUpsOff(2) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Setting this variable to turnUpsOff(2) causes
                the UPS to shut off.  When in this state, the UPS
                will not provide output power regardless of the input
                line state.  The on/off switch on the UPS
                must be toggled for the UPS to return to operation.
                                
                Setting this value to noTurnUpsOff(1) has no
                effect.
                                
                The value noTurnUpsOff(1) will always be returned
                when the variable is read."
   ::= { upsSmartControl 1 }


upsSmartControlRebootUps OBJECT-TYPE
        SYNTAX INTEGER {
                        noRebootUps(1),
                        rebootUps(2) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Setting this variable to rebootUps(2) causes the
                UPS to shut off and turn back on.
                                
                Setting this value to noRebootUps(1) has no effect.
                                
                The value noRebootUps(1) will always be returned
                when the variable is read."
   ::= { upsSmartControl 2 }


upsSmartControlUpsSleep OBJECT-TYPE
        SYNTAX INTEGER {
                        noPutUpsToSleep(1),
                        putUpsToSleep(2) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Setting this variable to putUpsToSleep(2) causes
                the UPS to go to sleep for the time specified by
                upsSmartConfigUpsSleepTime.
                                
                When in sleep mode, the UPS will not provide output
                power regardless of the input line state.  Once the
                specified time has elapsed, output power will be
                restored.
                                
                Setting this value to noPutUpsToSleep(1) has no
                effect.
                                
                The value noPutUpsToSleep(1) will always be returned
                when the variable is read."
   ::= { upsSmartControl 3 }


upsSmartControlSimulatePowerFail OBJECT-TYPE
        SYNTAX INTEGER {
                        noSimulatePowerFailure(1),
                        simulatePowerFailure(2) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Setting this variable to simulatePowerFailure(2) causes
                the UPS switch to battery power.
                                
                Setting this value to noSimulatePowerFailure(1) has no
                effect.
                                
                The value noSimulatePowerFailure(1) will always be returned
                when the variable is read."
   ::= { upsSmartControl 4 }


upsSmartControlFlashAndBeep OBJECT-TYPE
        SYNTAX INTEGER {
                        noFlashAndBeep(1),
                        flashAndBeep(2) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "UPS to identify itself by lighting all indicators
                and beeping.
                                
                Setting this variable to FlashAndBeep(2) causes
                the UPS lights all panel indicators and beeps.
                                
                Setting this value to noFlashAndBeep(1) has no
                effect.
                                
                The value noFlashAndBeep(1) will always be returned
                when the variable is read."
   ::= { upsSmartControl 5 }


upsSmartControlTurnOnUpsLoad OBJECT-TYPE
        SYNTAX INTEGER {
                        noUpsSmartControlTurnOnUpsLoad(1),
                        upsSmartControlTurnOnUpsLoad(2) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Setting this variable to upsSmartControlTurnOnUpsLoad(2)
                causes the UPS switch back to utility power if utility
                power is present.
                                
                Setting this value to noUpsSmartControlTurnOnUpsLoad(1)
                has no effect.
                                
                The value noUpsSmartControlTurnOnUpsLoad(1) will always
                be returned when the variable is read."
   ::= { upsSmartControl 6 }


-- the upsBaseTest group
-- the upsSmartTest group

upsSmartTestDiagnosticSchedule OBJECT-TYPE
        SYNTAX INTEGER {
                        unknown(1),
                        biweekly(2),
                        weekly(3),
                        never(4) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "The UPS system's automatic battery test schedule."
  ::= { upsSmartTest 1 }


upsSmartTestDiagnostics OBJECT-TYPE
        SYNTAX INTEGER {
                        noTestDiagnostics(1),
                        testDiagnostics(2) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Setting this variable to testDiagnostics(2) causes
                the UPS to perform a diagnostic self test.
                                
                Setting this value to noTestDiagnostics(1) has no
                effect.
                                
                The value noTestDiagnostics(1) will always be returned
                when the variable is read."
   ::= { upsSmartTest 2 }


upsSmartTestDiagnosticsResults OBJECT-TYPE
        SYNTAX INTEGER {
                        ok(1),
                        failed(2),
                        invalidTest(3),
                        testInProgress(4) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The results of the last UPS diagnostics test performed."
   ::= { upsSmartTest 3 }


upsSmartTestLastDiagnosticsDate OBJECT-TYPE
        SYNTAX DisplayString
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The date the last UPS diagnostics test was performed in
                mm/dd/yy format."
   ::= { upsSmartTest 4 }


upsSmartTestIndicators OBJECT-TYPE
        SYNTAX INTEGER {
                        noTestIndicators(1),
                        testIndicators(2) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Setting this variable to testIndicators(2) causes
                the UPS to perform a front panel indicator (lights) test.
                                
                Setting this value to noTestIndicators(1) has no effect.
                                
                The value noTestIndicators(1) will always be returned
                when the variable is read."
   ::= { upsSmartTest 5 }


upsSmartTestRuntimeCalibration OBJECT-TYPE
        SYNTAX INTEGER {
                        noPerformCalibration(1),
                        performCalibration(2),
                        cancelCurrentCalibration(3) }
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Setting this variable to performCalibration(2) causes
                the UPS to discharge to calibrate the UPS.
                The test will only start if the battery capacity is 100 percent.
                The test runs until capacity is less than 25 percent.
                                
                Setting this variable to cancelCurrentCalibration(3)
                after setting performCalibration(2) will cancel the
                current discharge.
                                
                Setting this variable to noPerformCalibration(1)
                will have no effect.
                                
                The value noPerformCalibration(1) will always be returned
                when the variable is read.
                                
                The result of the calibration will be saved in
                upsSmartTestCalibrationResult."
   ::= { upsSmartTest 6 }


upsSmartTestCalibrationResults OBJECT-TYPE
        SYNTAX INTEGER {
                        ok(1),
                        invalidTest(2),
                        calibrationInProgress(3) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The results of the last runtime calibration.
                                
                Value ok(1) means a successful runtime calibration.
                                
                Value invalidTest(2) indicates last calibration did
                not take place since the battery capacity was below
                100 percent.
                                
                Value calibrationInProgress(3) means a calibration
                is occurring now."
   ::= { upsSmartTest 7 }


upsSmartTestCalibrationDate OBJECT-TYPE
        SYNTAX DisplayString
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The date the last UPS runtime calibration was
                performed in mm/dd/yy format."
   ::= { upsSmartTest 8 }


-----------------------
--ups ThreePhase group-
-----------------------
upsThreePhaseBatteryVoltage OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Battery Voltage"
   ::= { upsThreePhaseBatteryGrp 1 }


upsThreePhaseBatteryCapacityPercentage OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Battery Capacity Percentage"
   ::= { upsThreePhaseBatteryGrp 2 }


upsThreePhaseBatteryTimeRemain OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Battery Time Remain (unit is Minute)"
   ::= { upsThreePhaseBatteryGrp 3 }


upsThreePhaseBatteryCurrent OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Battery Electric Current"
   ::= { upsThreePhaseBatteryGrp 4 }


upsThreePhaseBatteryTemperature OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Battery Temperature"
   ::= { upsThreePhaseBatteryGrp 5 }


upsThreePhaseInputFrequency OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Input Frequency"
   ::= { upsThreePhaseInputGrp 1 }


upsThreePhaseInputVoltageR OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Input VoltageR"
   ::= { upsThreePhaseInputGrp 2 }


upsThreePhaseInputVoltageS OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Input VoltageS"
   ::= { upsThreePhaseInputGrp 3 }


upsThreePhaseInputVoltageT OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Input VoltageT"
   ::= { upsThreePhaseInputGrp 4 }


upsThreePhaseOutputFrequency OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Output Frequency"
   ::= { upsThreePhaseOutputGrp 1 }


upsThreePhaseOutputVoltageR OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Output VoltageR"
   ::= { upsThreePhaseOutputGrp 2 }


upsThreePhaseOutputVoltageS OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Output VoltageS"
   ::= { upsThreePhaseOutputGrp 3 }


upsThreePhaseOutputVoltageT OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Output VoltageT"
   ::= { upsThreePhaseOutputGrp 4 }


upsThreePhaseOutputLoadPercentageR OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Load PercentageR"
   ::= { upsThreePhaseOutputGrp 5 }


upsThreePhaseOutputLoadPercentageS OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Load PercentageS"
   ::= { upsThreePhaseOutputGrp 6 }


upsThreePhaseOutputLoadPercentageT OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Load PercentageT"
   ::= { upsThreePhaseOutputGrp 7 }


upsThreePhaseBypassSourceFrequency OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Bypass Frequency"
   ::= { upsThreePhaseBypassGrp 1 }


upsThreePhaseBypssSourceVoltageR OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Bypass VoltageR"
   ::= { upsThreePhaseBypassGrp 2 }


upsThreePhaseBypssSourceVoltageS OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Bypass VoltageS"
   ::= { upsThreePhaseBypassGrp 3 }


upsThreePhaseBypssSourceVoltageT OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Bypass VoltageT"
   ::= { upsThreePhaseBypassGrp 4 }


upsThreePhaseDCandRectifierStatusRecRotError OBJECT-TYPE
        SYNTAX INTEGER {
                        yes(14),
                        no(16) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Rectifier Rotation Error"
   ::= { upsThreePhaseDCandRectifierStatusGrp 1 }


upsThreePhaseDCandRectifierStatusLowBatteryShutdown OBJECT-TYPE
        SYNTAX INTEGER {
                        yes(14),
                        no(16) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Low Battery Shutdown"
   ::= { upsThreePhaseDCandRectifierStatusGrp 2 }


upsThreePhaseDCandRectifierStatusLowBattery OBJECT-TYPE
        SYNTAX INTEGER {
                        yes(14),
                        no(16) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Low Battery"
   ::= { upsThreePhaseDCandRectifierStatusGrp 3 }


upsThreePhaseDCandRectifierStatusInAndOut OBJECT-TYPE
        SYNTAX INTEGER {
                        threeInOneOut(2),
                        threeInThreeOut(3) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "In And Put"
   ::= { upsThreePhaseDCandRectifierStatusGrp 4 }


upsThreePhaseDCandRectifierStatusBatteryStatus OBJECT-TYPE
        SYNTAX INTEGER {
                        backup(4),
                        acnormal(5) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Back Status"
   ::= { upsThreePhaseDCandRectifierStatusGrp 5 }


upsThreePhaseDCandRectifierStatusChargeStatus OBJECT-TYPE
        SYNTAX INTEGER {
                        boost(6),
                        float(7),
                        no(16) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Charge Status"
   ::= { upsThreePhaseDCandRectifierStatusGrp 6 }


upsThreePhaseDCandRectifierStatusRecOperating OBJECT-TYPE
        SYNTAX INTEGER {
                        yes(14),
                        no(16) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Rectifier Operating"
   ::= { upsThreePhaseDCandRectifierStatusGrp 7 }


upsThreePhaseUPSStatusBypassFreqFail OBJECT-TYPE
        SYNTAX INTEGER {
                        yes(14),
                        no(16) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Bypass Status"
   ::= { upsThreePhaseUPSStatusGrp 1 }


upsThreePhaseUPSStatusManualBypassBreaker OBJECT-TYPE
        SYNTAX INTEGER {
                        close(8),
                        open(9) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Breaker Status"
   ::= { upsThreePhaseUPSStatusGrp 2 }


upsThreePhaseUPSStatusACStatus OBJECT-TYPE
        SYNTAX INTEGER {
                        normal(10),
                        abnormal(11) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "AC Status"
   ::= { upsThreePhaseUPSStatusGrp 3 }


upsThreePhaseUPSStaticSwitchMode OBJECT-TYPE
        SYNTAX INTEGER {
                        invermode(12),
                        bypassmode(13) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Switch Mode"
   ::= { upsThreePhaseUPSStatusGrp 4 }


upsThreePhaseUPSStatusInverterOperating OBJECT-TYPE
        SYNTAX INTEGER {
                        yes(14),
                        no(16) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Operating"
   ::= { upsThreePhaseUPSStatusGrp 5 }


upsThreePhaseFaultStatusEmergencyStop OBJECT-TYPE
        SYNTAX INTEGER {
                        yes(14),
                        no(16) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Emergency Stop"
   ::= { upsThreePhaseFaultStatusGrp 1 }


upsThreePhaseFaultStatusHighDCShutdown OBJECT-TYPE
        SYNTAX INTEGER {
                        yes(14),
                        no(16) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "High DC Shutdown"
   ::= { upsThreePhaseFaultStatusGrp 2 }


upsThreePhaseFaultStatusBypassBreaker OBJECT-TYPE
        SYNTAX INTEGER {
                        yes(14),
                        no(16) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Bypass Breaker"
   ::= { upsThreePhaseFaultStatusGrp 3 }


upsThreePhaseFaultStatusOverLoad OBJECT-TYPE
        SYNTAX INTEGER {
                        yes(14),
                        no(16) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Over Load"
   ::= { upsThreePhaseFaultStatusGrp 4 }


upsThreePhaseFaultStatusInverterOutputFail OBJECT-TYPE
        SYNTAX INTEGER {
                        yes(14),
                        no(16) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Output Fail"
   ::= { upsThreePhaseFaultStatusGrp 5 }


upsThreePhaseFaultStatusOverTemperature OBJECT-TYPE
        SYNTAX INTEGER {
                        yes(14),
                        no(16) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Over Temperature"
   ::= { upsThreePhaseFaultStatusGrp 6 }


upsThreePhaseFaultStatusShortCircuit OBJECT-TYPE
        SYNTAX INTEGER {
                        yes(14),
                        no(16) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Short Circuit"
   ::= { upsThreePhaseFaultStatusGrp 7 }


upsThreePhaseRatingRectifierVoltage OBJECT-TYPE
        SYNTAX DisplayString
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Rectifier Voltage"
   ::= { upsThreePhaseRatingGrp 1 }


upsThreePhaseRatingRectifierFrequency OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Rectifier Frequency"
   ::= { upsThreePhaseRatingGrp 2 }


upsThreePhaseRatingBypassVoltage OBJECT-TYPE
        SYNTAX DisplayString
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Bypass Voltage"
   ::= { upsThreePhaseRatingGrp 3 }


upsThreePhaseRatingBypassFrequency OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Bypass Frequency"
   ::= { upsThreePhaseRatingGrp 4 }


upsThreePhaseRatingOutputVoltage OBJECT-TYPE
        SYNTAX DisplayString
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Output Voltage"
   ::= { upsThreePhaseRatingGrp 5 }


upsThreePhaseRatingOutputFrequency OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Output Frequency"
   ::= { upsThreePhaseRatingGrp 6 }


upsThreePhaseRatingBatteryVoltage OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Battery Voltage"
   ::= { upsThreePhaseRatingGrp 7 }


upsThreePhaseRatingPower OBJECT-TYPE
        SYNTAX DisplayString
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Power Rating"
   ::= { upsThreePhaseRatingGrp 8 }


-----------------------
-----------------------

upsEnvStatus OBJECT IDENTIFIER  ::= { upsEnvironment 1 }

upsEnvTemperature OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The ambient environment temperature."
        ::= { upsEnvStatus 1 }


upsEnvHumidity OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "The environment humidity."
        ::= { upsEnvStatus 2 }


upsEnvOverTemperature OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Alarm dupsAlarmOverTemperature on when the environment
                temperature over the value."
        ::= { upsEnvSetting 1 }


upsEnvOverHumidity OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Alarm dupsAlarmOverHumidity on when the environment
                humidity over the value."
        ::= { upsEnvSetting 3 }


upsEnvSecurity1 OBJECT-TYPE
        SYNTAX INTEGER {
                        normal(1),
                        abnormal(2) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Security status"
        ::= { upsEnvStatus 5 }


upsEnvSecurity2 OBJECT-TYPE
        SYNTAX INTEGER {
                        normal(1),
                        abnormal(2) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Security status"
        ::= { upsEnvStatus 6 }


upsEnvSecurity3 OBJECT-TYPE
        SYNTAX INTEGER {
                        normal(1),
                        abnormal(2) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Security status"
        ::= { upsEnvStatus 7 }


upsEnvSecurity4 OBJECT-TYPE
        SYNTAX INTEGER {
                        normal(1),
                        abnormal(2) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Security status"
        ::= { upsEnvStatus 8 }


upsEnvSecurity5 OBJECT-TYPE
        SYNTAX INTEGER {
                        normal(1),
                        abnormal(2) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Security status"
        ::= { upsEnvStatus 9 }


upsEnvSecurity6 OBJECT-TYPE
        SYNTAX INTEGER {
                        normal(1),
                        abnormal(2) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Security status"
        ::= { upsEnvStatus 10 }


upsEnvSecurity7 OBJECT-TYPE
        SYNTAX INTEGER {
                        normal(1),
                        abnormal(2) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Security status"
        ::= { upsEnvStatus 11 }


upsEnvWater OBJECT-TYPE
        SYNTAX INTEGER {
                        normal(1),
                        abnormal(2) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Water status"
        ::= { upsEnvStatus 3 }


upsEnvSmoke OBJECT-TYPE
        SYNTAX INTEGER {
                        normal(1),
                        abnormal(2) }
        ACCESS read-only
        STATUS mandatory
        DESCRIPTION
                "Smoke status"
        ::= { upsEnvStatus 4 }


upsEnvSetting OBJECT IDENTIFIER         ::= { upsEnvironment 2 }

upsEnvUnderTemperature OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Alarm dupsAlarmUnderTemperature on when the environment
                temperature below the value."
        ::= { upsEnvSetting 2 }


upsEnvUnderHumidity OBJECT-TYPE
        SYNTAX INTEGER
        ACCESS read-write
        STATUS mandatory
        DESCRIPTION
                "Alarm dupsAlarmUnderHumidity on when the environment
                humidity below the value."
        ::= { upsEnvSetting 4 }



communicationLost TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "SEVERE: Communication to the UPS has been lost.  Steps
                to reestablish communication are in progress."
        --#TYPE "PPC UPS: Communication failure"
        --#SUMMARY "Communication to the UPS has been lost."
        --#ARGUMENTS { }
        --#SEVERITY CRITICAL
        --#TIMEINDEX 1
        --#HELP ""
        --#HELPTAG 0
        --#STATE DEGRADED
 ::= 1



upsOverLoad TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "SEVERE: The UPS has sensed a load greater than 100 percent
                of its rated capacity."
        --#TYPE "PPC UPS: UPS overload"
        --#SUMMARY "The UPS has sensed a load greater than 100 percent of its rated capacity."
        --#ARGUMENTS { }
        --#SEVERITY CRITICAL
        --#TIMEINDEX 1
        --#HELP ""
        --#HELPTAG 0
        --#STATE DEGRADED
 ::= 2



upsDiagnosticsFailed TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "SEVERE: The UPS failed its internal diagnostic self-test."
        --#TYPE "PPC UPS: Failed self-test"
        --#SUMMARY "The UPS has failed its internal diagnostic self-test."
        --#ARGUMENTS { }
        --#SEVERITY CRITICAL
        --#TIMEINDEX 1
        --#HELP ""
        --#HELPTAG 0
        --#STATE DEGRADED
 ::= 3



upsDischarged TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "SEVERE: The UPS just started a runtime calibration
                discharge.  The UPS batteries are being discharged."
        --#TYPE "PPC UPS: Deep discharge"
        --#SUMMARY "The UPS has just started a runtime calibration discharge."
        --#ARGUMENTS { }
        --#SEVERITY CRITICAL
        --#TIMEINDEX 1
        --#HELP ""
        --#HELPTAG 0
        --#STATE DEGRADED
 ::= 4



upsOnBattery TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: The UPS has switched to battery backup power."
        --#TYPE "PPC UPS: On battery"
        --#SUMMARY "The UPS has switched to battery backup power."
        --#ARGUMENTS { }
        --#SEVERITY MAJOR
        --#TIMEINDEX 1
        --#HELP ""
        --#HELPTAG 0
        --#STATE OPERATIONAL
 ::= 5



boostOn TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: The UPS has enabled Boost."
        --#TYPE "PPC UPS: SmartBoost"
        --#SUMMARY "The UPS has enabled Boost."
        --#ARGUMENTS { }
        --#SEVERITY MINOR
        --#TIMEINDEX 1
        --#HELP ""
        --#HELPTAG 0
        --#STATE OPERATIONAL
 ::= 6



lowBattery TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "SEVERE: The UPS batteries are low and will soon be exhausted.
                If utility power is not restored the UPS will put itself
                to 'sleep' and immediately cut power to the load."
        --#TYPE "PPC UPS: Low battery"
        --#SUMMARY "The UPS batteries are low and will soon be exhausted."
        --#ARGUMENTS { }
        --#SEVERITY CRITICAL
        --#TIMEINDEX 1
        --#HELP ""
        --#HELPTAG 0
        --#STATE DEGRADED
 ::= 7



communicationEstablished TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "INFORMATION: Communication with the UPS has been
                established."
        --#TYPE "PPC UPS: Communication established"
        --#SUMMARY "Communication with the UPS has been established."
        --#ARGUMENTS { }
        --#SEVERITY INFORMATIONAL
        --#TIMEINDEX 1
        --#HELP ""
        --#HELPTAG 0
        --#STATE OPERATIONAL
 ::= 8



powerRestored TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "INFORMATION: Utility power has been restored."
        --#TYPE "PPC UPS: Utility restored"
        --#SUMMARY "Normal power has been restored to the UPS."
        --#ARGUMENTS { }
        --#SEVERITY INFORMATIONAL
        --#TIMEINDEX 1
        --#HELP ""
        --#HELPTAG 0
        --#STATE OPERATIONAL
 ::= 9



upsDiagnosticsPassed TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "INFORMATION: The UPS passed its internal self-test."
        --#TYPE "PPC UPS: Passed self-test"
        --#SUMMARY "The UPS has passed its internal self-test."
        --#ARGUMENTS { }
        --#SEVERITY INFORMATIONAL
        --#TIMEINDEX 1
        --#HELP ""
        --#HELPTAG 0
        --#STATE OPERATIONAL
 ::= 10



returnFromLowBattery TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "INFORMATION: The UPS has returned from a low battery
                condition."
        --#TYPE "PPC UPS: Battery normal"
        --#SUMMARY "The UPS has returned from a low battery condition."
        --#ARGUMENTS { }
        --#SEVERITY INFORMATIONAL
        --#TIMEINDEX 1
        --#HELP ""
        --#HELPTAG 0
        --#STATE OPERATIONAL
 ::= 11



upsTurnedOff TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: The UPS has been turned 'off' by the
                management station."
        --#TYPE "PPC UPS: Switching off"
        --#SUMMARY "The UPS is being switched off by a management station."
        --#ARGUMENTS { }
        --#SEVERITY MAJOR
        --#TIMEINDEX 1
        --#HELP ""
        --#HELPTAG 0
        --#STATE NONOPERATIONAL
 ::= 12



upsSleeping TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: The UPS is entering 'sleep' mode.  Power
                to the load will be cut off."
        --#TYPE "PPC UPS: Going to sleep"
        --#SUMMARY "The UPS is going into sleep mode."
        --#ARGUMENTS { }
        --#SEVERITY MAJOR
        --#TIMEINDEX 1
        --#HELP ""
        --#HELPTAG 0
        --#STATE NONOPERATIONAL
 ::= 13



upsWokeUp TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "INFORMATION: The UPS woke up from 'sleep' mode.  Power
                to the load has been restored."
        --#TYPE "PPC UPS: Wake up"
        --#SUMMARY "The UPS has woke up from sleep mode."
        --#ARGUMENTS { }
        --#SEVERITY INFORMATIONAL
        --#TIMEINDEX 1
        --#HELP ""
        --#HELPTAG 0
        --#STATE OPERATIONAL
 ::= 14



upsRebootStarted TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: The UPS has started its reboot sequence.  After
                the specified delay the UPS will perform a reboot."
        --#TYPE "PPC UPS: Starting reboot"
        --#SUMMARY "The UPS has started its reboot sequence."
        --#ARGUMENTS { }
        --#SEVERITY MAJOR
        --#TIMEINDEX 1
        --#HELP ""
        --#HELPTAG 0
        --#STATE NONOPERATIONAL
 ::= 15


envOverTemperature TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: The environment temperature exceed the normal value."
 ::= 16


envTemperatureNormal TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "INFORMATION: The environment temperature is normal."
 ::= 17


envOverHumidity TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: The environment humidity exceed the normal value."
 ::= 18


envHumidityNormal TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "INFORMATION: The environment humidity is normal."
 ::= 19


envSmokeAbnormal TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: Smoke is abnormal."
 ::= 20


envWaterAbnormal TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: Water is abnormal."
 ::= 21


envSecurityAbnormal TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: Security is abnormal."
 ::= 22


--envSmokeNormal TRAP-TYPE
--      ENTERPRISE ppc
--      DESCRIPTION 
--              "INFORMATION: Smoke is normal."
-- ::= 23


envWaterNormal TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "INFORMATION: Water is normal."
 ::= 24


--envSecurityNormal TRAP-TYPE
--      ENTERPRISE ppc
--      DESCRIPTION 
--              "INFORMATION: Security is normal."
-- ::= 25


envGasAbnormal TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: Gas Alarm"
 ::= 26


upsTemp TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: UPS Temperature Overrun"
 ::= 27


upsLoadNormal TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: UPS Load Normal"
 ::= 28


upsTempNormal TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: UPS temperature Normal"
 ::= 29


envUnderTemperature TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: The environment temperature below the normal value."
 ::= 30


envUnderHumidity TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: The environment humidity below the normal value."
 ::= 31


upsBypass TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: The UPS is entering 'bypass' mode."
 ::= 32


envSecurity1 TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: Security1 Alarm."
 ::= 33


envSecurity2 TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: Security2 Alarm."
 ::= 34


envSecurity3 TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: Security3 Alarm."
 ::= 35


envSecurity4 TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: Security4 Alarm."
 ::= 36


envSecurity5 TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: Security5 Alarm."
 ::= 37


envSecurity6 TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: Security6 Alarm."
 ::= 38


envSecurity7 TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: Security7 Alarm."
 ::= 39


--envSecurity1Return TRAP-TYPE
--      ENTERPRISE ppc
--      DESCRIPTION 
--              "WARNING: Security1 Normal."
-- ::= 40


--envSecurity2Return TRAP-TYPE
--      ENTERPRISE ppc
--      DESCRIPTION 
--              "WARNING: Security2 Normal"
-- ::= 41


--envSecurity3Return TRAP-TYPE
--      ENTERPRISE ppc
--      DESCRIPTION 
--              "WARNING: Security3 Normal."
-- ::= 42


--envSecurity4Return TRAP-TYPE
--      ENTERPRISE ppc
--      DESCRIPTION 
--              "WARNING: Security4 Normal."
-- ::= 43


--envSecurity5Return TRAP-TYPE
--      ENTERPRISE ppc
--      DESCRIPTION 
--              "WARNING: Security5 Normal."
-- ::= 44


--envSecurity6Return TRAP-TYPE
--      ENTERPRISE ppc
--      DESCRIPTION 
--              "WARNING: Security6 Normal."
-- ::= 45


--envSecurity7Return TRAP-TYPE
--      ENTERPRISE ppc
--      DESCRIPTION 
--              "WARNING: Security7 Normal."
-- ::= 46


upsRecroterror TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: Rectifier Rotation Error"
 ::= 47


upsBypassFreFail TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: Bypass Frequency Fail"
 ::= 48


upsBypassacnormal TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: Bypass AC Normal"
 ::= 49


upsBypassacabnormal TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: Bypass AC Abnormal"
 ::= 50


upsTest TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: UPS Test"
 ::= 51


upsScheduleShutdown TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: UPS Schedule Shutdown"
 ::= 52

upsBypassReturn TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "The UPS return from Bypass Mode"
 ::= 53

upsShortCircuitShutdown TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "The UPS Short Circuit Shutdown"
 ::= 54
 
upsInverterOutputFailShutdown TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "The UPS Inverter Output Fail Shutdown"
 ::= 55
 
upsBypassBreadkerOnShutdown TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "The UPS Manual Bypass Breaker on Shutdown"
 ::= 56
 
upsHighDCShutdown TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "The UPS High DC Shutdown"
 ::= 57
 
upsEmergencyStop TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "The UPS Emergency Stop"
 ::= 58
 
upsInverterMode TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "The UPS Static Switch in Inverter Mode"
 ::= 59
 
upsBypassMode TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "The UPS Static Switch in Bypass Mode"
 ::= 60
 
upsOverTemperatureShutdown TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "The UPS Over Temperature Shutdown"
 ::= 61
 
upsOverLoadShutdown TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "The UPS Overload Shutdown"
 ::= 62
 
upsCapacityUnderrun TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "The UPS Capacity Underrun"
 ::= 63
 
upsCapacityNormal TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "The UPS Capacity Normal"
 ::= 64
 
upsLowBatteryShutdown TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "The UPS Low Battery Shutdown"
 ::= 67
 
buckOn TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: The UPS has enabled Buck."
 ::= 68
 
returnFromBuck TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: The UPS has return from Buck."
 ::= 69
 
returnFromBoost TRAP-TYPE
        ENTERPRISE ppc
        DESCRIPTION 
                "WARNING: The UPS has return from Boost."
 ::= 70
 
END